Back to Case Studies
National Park ServiceMaintenance BuildingFederal Facility

National Monument Maintenance Building: 324 Issues Including Critical Life Safety & Structural Violations

A comprehensive plan review of a National Park Service maintenance building uncovered 324 issues including critical life safety violations, structural design conflicts, inadequate geotechnical investigation, and extensive code compliance errors—before permit submission.

324
Total Issues
20
Critical
5
High
0
Medium

The Project

A National Park Service maintenance building project at Craters of the Moon National Monument. InspectMind performed a comprehensive plan review of the architectural and structural drawings, identifying critical life safety violations, structural design conflicts, inadequate geotechnical investigation, exposed foam plastic in non-sprinklered building, and extensive code compliance errors before permit submission.

2021 International Building CodeIBC 1008.2 (Egress Illumination)IBC 1803.6 (Geotechnical Reports)IBC 2603.4 (Foam Plastic)NFPA 70 (NEC)IBC 1008.3 (Emergency Power)

Critical Findings (20)

CriticalAutomatic Shutoff of Required Emergency Egress Illumination

Fixture EW2EM is designated as an emergency exterior fixture intended for path of travel illumination. It is specified as having an "INTEGRAL OCCUPANCY SENSOR." According to the Lighting Sequence of Operation, sequence iO1 (which corresponds to fixtures with an integral occupancy sensor) is programmed for "AUTOMATIC OFF" after a 15-minute timeout. This directly contradicts IBC Section 1008.2, which requires means of egress illumination to be provided at all times the space is occupied, and Section 1008.3.2, which requires emergency systems to automatically illuminate exterior landings upon power failure.

Code: 2021 International Building Code

CriticalUse of used/unlisted fixtures for emergency egress illumination

Lighting Fixture Specific Note 3 explicitly permits the contractor to purchase 'a used fixture from an online retailer such as eBay' for fixture type EW1EM. This fixture is designated as a historically compatible unit connected to an emergency inverter for means of egress illumination. IBC Section 2702.1.3 requires emergency systems to be installed in accordance with NFPA 70, which mandates that electrical equipment be listed and approved. A used fixture from an unvetted source cannot be verified to meet listing requirements (such as UL) or the 90-minute emergency duration required by IBC Section 1008.3.4.

Code: 2021 International Building Code

CriticalUnconstructable Collector Plate Fastener Layout and Dimensional Conflict

The 'PLAN VIEW' of the collector plate on drawing I-S401 contains multiple geometric impossibilities. First, the specified transverse fastener pattern width totals 7.5 inches (3/4" + 6" + 3/4"), which is impossible to fit on the specified 7-inch wide plate ('COLLECTOR PL 1/4x7'). Additionally, the 1.5-inch transverse fastener spacing contradicts the requirement that fasteners be centered on the '2x' decking members ('CL BOLTS = CL 2x, TYP'). Per IBC 2304.2 and 2301.2, nominal 2x3 lumber (specified in Detail 09) has an actual width of 2.5 inches. A 1.5-inch bolt spacing across the boards would cause fasteners to miss the center of the structural members, violating the specified design intent and basic principles of structural sizing in IBC Chapter 23.

Code: 2021 International Building Code

CriticalInadequate Geotechnical Investigation and Foundation Design Basis

Drawing 0-S001, Foundation Design Note 1, explicitly states that the geotechnical report used for design (Report No. 17115.000) was 'prepared for the neighboring site and not intended for this project' and should be used for 'general reference only.' It further states that design recommendations are 'guidelines' that may be 'further modified by the special inspector's judgment during construction.' This violates IBC 1803.6, which requires a project-specific geotechnical report to be submitted at the time of permit application. Furthermore, IBC 1803.1 requires that geotechnical investigations and engineering calculations (design basis) be conducted by a registered design professional, not a special inspector during construction.

Code: 2021 International Building Code

CriticalRecirculation Pump Selection Incapable of Meeting Scheduled Performance Requirements

The 'RECIRCULATION PUMP SCHEDULE' specifies RCP-1 with a performance duty of 10 GPM at 17 FT of head, using a Bell & Gossett PL-30B as the Basis of Design. However, the manufacturer's performance curve for the PL-30B indicates a maximum shut-off head of approximately 17-18 FT. At the scheduled head of 17 FT, the pump's flow rate will be near zero GPM, making it physically incapable of delivering the required 10 GPM flow.

CriticalInadequate foundation depth at shed addition exterior wall

Section 2 showing the shed addition exterior wall (W2) and foundation assembly depicts the slab edge with insufficient embedment into the ground. The exterior grade line is shown meeting the wall above the bottom of the slab, but the graphical proportions of the slab (which matches the thickness of the 6-inch stud wall) indicate a total embedment depth of only a few inches. IBC Section 1809.4 requires that the minimum depth of footings below the undisturbed ground surface shall be 12 inches.

Code: 2021 International Building Code

CriticalExposed Spray Foam in Non-Sprinklered Building

Detail 4 shows "SPRAY FOAM INSULATION" applied at the roof deck and top of wall, exposed to the interior space (no thermal barrier shown). The Code Summary states the Snow Equipment Building is "NON-SPRINKLERED". Per IBC 2603.4 (under the applicable code), foam plastic insulation must be separated from the interior by a thermal barrier (e.g., 1/2" gypsum board) unless specific testing allows otherwise. Leaving standard spray foam exposed in a non-sprinklered building is a code violation.

CriticalContradictory Location of Option 06 Addition

The specification explicitly defines Option 06 as the construction of Bay 03 "TO THE EAST" of the new Snow Equipment Building. However, the drawing elevations indicate "OPTION 06" is located on the West side of the building (labeled at Grid 16-17, which is the left side of the South Elevation and right side of the North Elevation, opposite the "BASE SCOPE" at Grid 14-16).

CriticalConflict Between Required Staff Access and Slab Demolition in Office Area

Keynote 26.02 requires the SCADA panel in Office 103 to remain operational and accessible to staff at all times during construction. However, the demolition plan shows the entire floor slab in Office 103 and the adjacent RR 102 (the only access path) is to be demolished, as indicated by the diagonal hatch. This directly contradicts IBC 3310.2 and 3302.1, which mandate that means of egress and required accessible means of egress be maintained during construction and alterations.

Code: 2021 International Building Code

CriticalPhysically Impossible Meter Box Dimensions (Detail 1)

Detail 1 specifies a "24"W X 13"L X 12"H CONCRETE METER BOX" for a 2" water meter assembly. A standard 2" water meter body alone (AWWA C700) typically has a lay length of 17 inches, and the complete assembly with setter/valves requires significantly more space (often a vault or 30"x48" box). The specified 13" length is physically too small to contain the 2" assembly.

CriticalContradiction in Sprinkler Requirements for Snow Equipment Building

The Code Summary specification explicitly states that the new Snow Equipment Building is to be non-sprinklered. However, the Utility Plan depicts a 'FIRE RISER ROOM' within this building and notes instructions to route a fire riser drain and connect a 4" water line to the fire service, indicating a sprinkler system is included.

CriticalScope Discrepancy Regarding Restroom Shower

The drawing General Note 4 and details indicate that a shower is to be provided in the new accessible restroom. However, the Project Specification (Code Summary) Project Description and Plumbing Fixtures analysis only list a "new restroom and kitchenette" and do not include a shower in the scope or fixture calculations. This is a direct contradiction in the project scope defined by the specification versus the drawing.

Sample High Priority Findings (5 Total)

HighMissing Fire Alarm Notification in Restroom

Plan 1 (the primary Fire Alarm Floor Plan) fails to provide any fire alarm notification appliances, specifically visual notification (strobes), within the room labeled EQUIP 002, which contains plumbing fixtures (sink and toilet) identifying it as a restroom. Section 907.2 requires that fire alarm systems provide occupant notification in accordance with Section 907.5. Restrooms are common-use areas where occupants may be isolated and must be provided with audible and visual notification. This omission is confirmed as an error because Plan 2 (Option 01) includes a visual notification appliance (labeled '75') in the same room, indicating the requirement was overlooked in the main plan.

Code: 2021 International Building Code

HighFire Department Connection (FDC) Location, Visibility, and Access Obstruction

The 'SITE PLAN - FIRE PROTECTION' shows an existing 4-inch underground fire service line (labeled '(E) 4"U.G FIRE SERVICE') entering the 'AREA OF WORK' building on its north side. The primary fire apparatus access road and parking areas are located to the south. Per IBC Section 912.2.1, the Fire Department Connection (FDC) must be located on the street side or facing the access road and be fully visible; an FDC on the north side is obscured by the building from the main point of fire department access. Additionally, the drawing shows multiple landscape symbols (trees and shrubs) along this north perimeter where the service enters, which would obstruct the 36-inch clear working space and immediate access required by IBC Sections 912.4 and 912.4.2.

Code: 2021 International Building Code

HighIncorrect Occupancy Classification of Office Space as Group U (Utility)

The drawing identifies the structure as a "UTILITY BUILDING" in the plan title, which implies a Group U (Utility and Miscellaneous) occupancy classification under IBC Section 312.1. However, the plan identifies the building's primary use as professional office space, with rooms explicitly labeled "OFFICE 107", "OFFICE 106B", "OFFICE 105", "OFFICE 104", and "OPEN OFFICE 106". Per IBC Section 304.1, buildings or portions thereof used for office, professional, or service-type transactions must be classified as Business Group B. IBC Section 302.1 requires structures to be classified based on their "intended purpose" and the nature of hazards to occupants.

Code: 2021 International Building Code

HighNon-compliant emergency power activation and circuiting instructions

General Note B directs the contractor to circuit all emergency lighting and exit signs to the 'nearest line voltage circuit.' This contradicts IBC 1008.3.1 and 1008.3.2, which require emergency illumination to automatically activate upon 'power supply failure in rooms and spaces.' If emergency fixtures are circuited to the 'nearest' available circuit rather than the specific branch circuit serving the normal lighting in that room (as required by NFPA 70 700.12(F), referenced via IBC 2701.1 and 2702.1.3), the units will fail to activate if the local lighting circuit fails (e.g., a branch breaker trip) while the 'nearest' circuit remains energized. Furthermore, General Note A states that batteries shall engage 'only after complete loss of power,' which potentially prevents activation during critical voltage drops or brownout conditions, violating the requirement to automatically provide power when primary power is 'lost' per IBC 2702.1.4.

Code: 2021 International Building Code

HighInsufficient lap length for epoxy-coated masonry reinforcement dowels at threshold

Detail 3 specifies 'EPOXY-COATED #4 DOWELS x 30"' for the connection between the stem wall and the vertical masonry reinforcement. According to IBC Section 2107.2.1, the minimum length of a lapped splice shall be not less than 40 bar diameters, and where epoxy-coated bars are used, this length must be increased by 50%. For a #4 bar (0.5-inch diameter), the required lap is 30 inches (40 * 0.5" * 1.5). Because the drawing specifies the total length of the dowel as 30 inches, it is physically impossible to provide the mandatory 30-inch lap while also maintaining the required embedment into the concrete stem wall.

Code: 2021 International Building Code

Issue Categories

Life Safety

Emergency egress illumination, exit signs, means of egress, and life safety code compliance

Structural

Foundation design, structural connections, reinforcement, seismic design, and structural code compliance

Fire Protection

Fire alarm systems, sprinkler systems, fire department connections, and fire code compliance

Electrical

Panel schedules, circuit protection, emergency power, grounding, and electrical code compliance

Accessibility

ADA compliance, accessible routes, fixture clearances, grab bars, and accessibility standards

Code Compliance

Building code violations, code edition conflicts, occupancy classification, and compliance requirements

Document Coordination

Drawing conflicts, schedule mismatches, sheet numbering errors, and document coordination issues

Value Delivered

324 issues surfaced before permit submission
20 critical life safety and structural violations identified
Inadequate geotechnical investigation and foundation design conflicts caught
Emergency egress illumination violations and electrical code conflicts resolved

"The automatic shutoff of emergency egress lighting and exposed foam plastic in a non-sprinklered building would have been instant permit rejections. Finding 324 issues—including 29 critical life safety violations—before submission saved us from weeks of redesign and potential safety failures."

— Project Team, National Park Service

Want This Level of Detail on Your Next Project?

Get comprehensive AI plan review with prioritized issues and code references.

5+ issues or full refund
Results in hours
Demo optional

One issue found pays for the whole check