Gymnasium Restoration: 84 Issues Flagged

Coordinate restoration scope, metal materials, and existing-service interfaces before repair pricing and field work.

84
Potential findings
3
Disciplines
3
Published examples
Start with $100 creditSee the findings

Enterprise & volume pricing

Anonymized review · Published 2026-09-16

What this review documents

Coordinate restoration scope, metal materials, and existing-service interfaces before repair pricing and field work.

The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.

Open the sample report →See pricing →Read our measurement definitions →

Key findings

Drain refurbishment detail describes replacement

Architectural / Plumbing

Critical

A schedule distinguishes drain refurbishment from replacement, but the refurbishment detail instructs removal of the drain body and installation of a new drain.

Next step: Confirm the required work at each drain and align the schedule and details.

Steel-plate specification references need reconciliation

Structural / Architectural

Critical

A repair detail references a carbon-steel plate section and an anchor specification containing stainless-plate requirements. The applicable plate material is unclear.

Next step: Clarify which specification governs the repair plate and its corrosion protection.

Stud cut around existing piping needs verification

Structural / Architectural

Critical

A detail shows a substantial opening in a steel stud around existing piping. The review questioned whether the cut is compatible with the framing requirements.

Next step: Have the designer verify the opening and provide an appropriate framing or reinforcement detail.

Issue categories

Architectural / Plumbing
Architectural / Plumbing findings in the selected review excerpts.
Structural / Architectural
Structural / Architectural findings in the selected review excerpts.

Review details and suggested questions

Drain refurbishment detail describes replacement
Architectural / Plumbing
Critical

Summary: A schedule distinguishes drain refurbishment from replacement, but the refurbishment detail instructs removal of the drain body and installation of a new drain.

Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.

Suggested next step: Confirm the required work at each drain and align the schedule and details.

RFI draft: Confirm the required work at each drain and align the schedule and details.

Steel-plate specification references need reconciliation
Structural / Architectural
Critical

Summary: A repair detail references a carbon-steel plate section and an anchor specification containing stainless-plate requirements. The applicable plate material is unclear.

Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.

Suggested next step: Clarify which specification governs the repair plate and its corrosion protection.

RFI draft: Clarify which specification governs the repair plate and its corrosion protection.

Stud cut around existing piping needs verification
Structural / Architectural
Critical

Summary: A detail shows a substantial opening in a steel stud around existing piping. The review questioned whether the cut is compatible with the framing requirements.

Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.

Suggested next step: Have the designer verify the opening and provide an appropriate framing or reinforcement detail.

RFI draft: Have the designer verify the opening and provide an appropriate framing or reinforcement detail.

Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.

Related case studies

Similar AI plan review results by project type and discipline. Browse all case studies

First $100 covered

Want this on your next set?

Start with the first $100 covered. See cited issues in hours, no call required.

  • Evidence-linked findings
  • 5+ issues or full refund
  • Results in hours

5+ issues or full refund · No demo required

View all case studies|See pricing