InspectMind AI logo InspectMind

Restaurant Permit Set: 175 Issues Found

An anonymized plan review of a full restaurant permit set uncovered food service, electrical, and MEP coordination issues before permit submission.

Free check on up to 10 drawing pages. Enterprise and volume pricing

Potential findings
175
Disciplines
6
Codes referenced
6
Critical or high examples shown
7

About this review

InspectMind ran an AI plan review on this project set and returned 175 potential findings across Food Service, Electrical, Architectural, Plumbing, Mechanical, Fire Protection. The selected examples below show the document conflict, why it matters, and a suggested next step.

Disciplines
Food Service, Electrical, Architectural, Plumbing, Mechanical, Fire Protection
Potential findings
175
Examples shown
15

Key findings

  1. Missing high-voltage designations for cooking equipment

    Electrical

    Critical

    Specifications require 480V/3-phase for major cooking equipment; electrical plans lack voltage labels at connection points.

  2. Missing specifications for equipment tags

    Architectural

    Critical

    Equipment tags on drawings have no corresponding specification entries; sequence gaps in spec section.

  3. Lighting fixtures without circuit identification

    Electrical

    Critical

    Lighting plan shows fixtures without circuit numbers or fixture type tags per general notes.

  4. Kitchen exhaust hood clearance and fire suppression

    Fire Protection

    High

    Hood clearance and fire suppression coverage need verification against IFC and NFPA 96.

  5. Grease interceptor and drainage coordination

    Plumbing

    High

    Drainage from food service equipment must connect to grease interceptor; routing not fully shown.

  6. Accessible route at service entrance

    Architectural

    High

    Service entrance and loading area may not meet accessible route requirements where public access is provided.

  7. Make-up air and kitchen exhaust balance

    Mechanical

    High

    Kitchen exhaust CFM and make-up air supply should be balanced per IMC; schedules not fully coordinated.

  8. Equipment schedule and plan tag consistency

    Food Service

    Medium

    Several equipment tags on plans do not match schedule numbering; some items skipped in sequence.

  9. Emergency power for critical kitchen loads

    Electrical

    Medium

    Critical refrigeration and cold storage may require emergency or optional standby power per code.

  10. Backflow prevention at hose connections

    Plumbing

    Medium

    Hose bibs and mop sinks in food service areas require appropriate backflow prevention per IPC.

Issue categories

Food Service
Food service equipment, kitchen layouts, and equipment specifications
Electrical
Electrical systems, high-voltage equipment, circuits, and NEC compliance
Architectural
Egress, accessibility, room layouts, and building code compliance
Plumbing
Plumbing fixtures, drainage, venting, and IPC compliance
Mechanical
HVAC, kitchen exhaust, and IMC compliance
Fire Protection
Fire suppression, alarms, and IFC compliance

Review details and suggested questions

Missing high-voltage designations for cooking equipment

Electrical

Critical

Summary: Specifications require 480V/3-phase for major cooking equipment; electrical plans lack voltage labels at connection points.

Why it matters: Risk of 120V rough-ins where 480V is required, leading to rework and equipment incompatibility.

Suggested next step: Confirm circuit requirements and add voltage labels on electrical plans.

RFI draft: Please confirm circuit requirements for cooking equipment and add high-voltage designations on the electrical plan.

Missing specifications for equipment tags

Architectural

Critical

Summary: Equipment tags on drawings have no corresponding specification entries; sequence gaps in spec section.

Why it matters: Equipment cannot be procured or installed without specifications.

Suggested next step: Provide missing specifications for all tagged equipment.

RFI draft: Please provide the missing specifications for the equipment tags shown on the plans.

Lighting fixtures without circuit identification

Electrical

Critical

Summary: Lighting plan shows fixtures without circuit numbers or fixture type tags per general notes.

Why it matters: Electrical contractor cannot reliably circuit lighting or match fixture schedule.

Suggested next step: Revise lighting plan to show circuit identification and fixture tags.

RFI draft: Please add circuit identification and fixture type tags per Note G on the lighting plan.

Kitchen exhaust hood clearance and fire suppression

Fire Protection

High

Summary: Hood clearance and fire suppression coverage need verification against IFC and NFPA 96.

Why it matters: Non-compliance can delay permit and require field changes.

Suggested next step: Verify hood details and suppression coverage on drawings and specs.

RFI draft: Please confirm hood clearance and fire suppression coverage per code.

Grease interceptor and drainage coordination

Plumbing

High

Summary: Drainage from food service equipment must connect to grease interceptor; routing not fully shown.

Why it matters: Missing or incorrect routing can cause code failures and rework.

Suggested next step: Show all FFE drain connections to grease interceptor on plumbing plan.

RFI draft: Please clarify drainage routing from food service equipment to grease interceptor.

Accessible route at service entrance

Architectural

High

Summary: Service entrance and loading area may not meet accessible route requirements where public access is provided.

Why it matters: ADA compliance is required for permit approval.

Suggested next step: Verify accessible route and provide compliant path or note exception.

RFI draft: Please confirm accessible route at service entrance per IBC Chapter 11.

Make-up air and kitchen exhaust balance

Mechanical

High

Summary: Kitchen exhaust CFM and make-up air supply should be balanced per IMC; schedules not fully coordinated.

Why it matters: Imbalance can affect equipment operation and code compliance.

Suggested next step: Coordinate exhaust and make-up air on mechanical drawings.

RFI draft: Please confirm make-up air capacity matches kitchen exhaust per IMC.

Equipment schedule and plan tag consistency

Food Service

Medium

Summary: Several equipment tags on plans do not match schedule numbering; some items skipped in sequence.

Why it matters: Inconsistency can cause procurement and installation errors.

Suggested next step: Align plan tags with equipment schedule and fill sequence gaps.

RFI draft: Please align equipment tags on plans with the equipment schedule.

Emergency power for critical kitchen loads

Electrical

Medium

Summary: Critical refrigeration and cold storage may require emergency or optional standby power per code.

Why it matters: Loss of power can cause food safety and code issues.

Suggested next step: Confirm emergency/standby requirements and show on electrical design.

RFI draft: Please confirm if emergency or optional standby power is required for refrigeration.

Backflow prevention at hose connections

Plumbing

Medium

Summary: Hose bibs and mop sinks in food service areas require appropriate backflow prevention per IPC.

Why it matters: Cross-connection risk to potable water system.

Suggested next step: Specify and detail backflow prevention at all hose connections.

RFI draft: Please confirm backflow prevention at hose bibs and mop sinks per IPC.

Egress width and door swing

Architectural

Medium

Summary: One egress path may not meet minimum width with door swing in use.

Why it matters: Life safety and permit approval depend on egress compliance.

Suggested next step: Verify egress width with doors in use and revise if needed.

RFI draft: Please verify egress width with door swing per IBC.

Fire-rated penetrations at kitchen walls

Fire Protection

Medium

Summary: Duct and pipe penetrations at fire-rated kitchen walls need firestop details.

Why it matters: Unprotected penetrations compromise fire rating.

Suggested next step: Provide firestop details for all penetrations in rated assemblies.

RFI draft: Please provide firestop details for penetrations in fire-rated kitchen walls.

Ventilation rate for dining area

Mechanical

Low

Summary: Outdoor air rate for dining area should be verified against IMC table.

Why it matters: Ensures acceptable IAQ and code compliance.

Suggested next step: Confirm ventilation rates on mechanical schedule.

RFI draft: Please confirm outdoor air rates for dining area per IMC.

Ground-fault protection for kitchen circuits

Electrical

Low

Summary: Kitchen receptacles and equipment circuits require GFCI or other protection per NEC.

Why it matters: Safety and code compliance.

Suggested next step: Verify GFCI and protection requirements on electrical design.

RFI draft: Please confirm GFCI protection for kitchen circuits per NEC.

Floor drain slope and location

Plumbing

Low

Summary: Floor drain locations and slope to drain should be confirmed for kitchen and back-of-house.

Why it matters: Proper drainage prevents standing water and code issues.

Suggested next step: Verify floor drain layout and slope on plumbing and floor plans.

RFI draft: Please confirm floor drain locations and slope to drain.

This is an anonymized example. Findings shown are excerpts for illustration. Actual project details have been modified to protect client confidentiality.