Restaurant Permit Set: 175 Issues Found
An anonymized plan review of a full restaurant permit set uncovered food service, electrical, and MEP coordination issues before permit submission.
Free check on up to 10 drawing pages. Enterprise and volume pricing
- Potential findings
- 175
- Disciplines
- 6
- Codes referenced
- 6
- Critical or high examples shown
- 7
About this review
InspectMind ran an AI plan review on this project set and returned 175 potential findings across Food Service, Electrical, Architectural, Plumbing, Mechanical, Fire Protection. The selected examples below show the document conflict, why it matters, and a suggested next step.
- Disciplines
- Food Service, Electrical, Architectural, Plumbing, Mechanical, Fire Protection
- Potential findings
- 175
- Examples shown
- 15
Key findings
- Critical
Missing high-voltage designations for cooking equipment
Electrical
Specifications require 480V/3-phase for major cooking equipment; electrical plans lack voltage labels at connection points.
- Critical
Missing specifications for equipment tags
Architectural
Equipment tags on drawings have no corresponding specification entries; sequence gaps in spec section.
- Critical
Lighting fixtures without circuit identification
Electrical
Lighting plan shows fixtures without circuit numbers or fixture type tags per general notes.
- High
Kitchen exhaust hood clearance and fire suppression
Fire Protection
Hood clearance and fire suppression coverage need verification against IFC and NFPA 96.
- High
Grease interceptor and drainage coordination
Plumbing
Drainage from food service equipment must connect to grease interceptor; routing not fully shown.
- High
Accessible route at service entrance
Architectural
Service entrance and loading area may not meet accessible route requirements where public access is provided.
- High
Make-up air and kitchen exhaust balance
Mechanical
Kitchen exhaust CFM and make-up air supply should be balanced per IMC; schedules not fully coordinated.
- Medium
Equipment schedule and plan tag consistency
Food Service
Several equipment tags on plans do not match schedule numbering; some items skipped in sequence.
- Medium
Emergency power for critical kitchen loads
Electrical
Critical refrigeration and cold storage may require emergency or optional standby power per code.
- Medium
Backflow prevention at hose connections
Plumbing
Hose bibs and mop sinks in food service areas require appropriate backflow prevention per IPC.
Issue categories
- Food Service
- Food service equipment, kitchen layouts, and equipment specifications
- Electrical
- Electrical systems, high-voltage equipment, circuits, and NEC compliance
- Architectural
- Egress, accessibility, room layouts, and building code compliance
- Plumbing
- Plumbing fixtures, drainage, venting, and IPC compliance
- Mechanical
- HVAC, kitchen exhaust, and IMC compliance
- Fire Protection
- Fire suppression, alarms, and IFC compliance
Review details and suggested questions
Missing high-voltage designations for cooking equipmentElectrical
Critical
Electrical
Summary: Specifications require 480V/3-phase for major cooking equipment; electrical plans lack voltage labels at connection points.
Why it matters: Risk of 120V rough-ins where 480V is required, leading to rework and equipment incompatibility.
Suggested next step: Confirm circuit requirements and add voltage labels on electrical plans.
RFI draft: Please confirm circuit requirements for cooking equipment and add high-voltage designations on the electrical plan.
Missing specifications for equipment tagsArchitectural
Critical
Architectural
Summary: Equipment tags on drawings have no corresponding specification entries; sequence gaps in spec section.
Why it matters: Equipment cannot be procured or installed without specifications.
Suggested next step: Provide missing specifications for all tagged equipment.
RFI draft: Please provide the missing specifications for the equipment tags shown on the plans.
Lighting fixtures without circuit identificationElectrical
Critical
Electrical
Summary: Lighting plan shows fixtures without circuit numbers or fixture type tags per general notes.
Why it matters: Electrical contractor cannot reliably circuit lighting or match fixture schedule.
Suggested next step: Revise lighting plan to show circuit identification and fixture tags.
RFI draft: Please add circuit identification and fixture type tags per Note G on the lighting plan.
Kitchen exhaust hood clearance and fire suppressionFire Protection
High
Fire Protection
Summary: Hood clearance and fire suppression coverage need verification against IFC and NFPA 96.
Why it matters: Non-compliance can delay permit and require field changes.
Suggested next step: Verify hood details and suppression coverage on drawings and specs.
RFI draft: Please confirm hood clearance and fire suppression coverage per code.
Grease interceptor and drainage coordinationPlumbing
High
Plumbing
Summary: Drainage from food service equipment must connect to grease interceptor; routing not fully shown.
Why it matters: Missing or incorrect routing can cause code failures and rework.
Suggested next step: Show all FFE drain connections to grease interceptor on plumbing plan.
RFI draft: Please clarify drainage routing from food service equipment to grease interceptor.
Accessible route at service entranceArchitectural
High
Architectural
Summary: Service entrance and loading area may not meet accessible route requirements where public access is provided.
Why it matters: ADA compliance is required for permit approval.
Suggested next step: Verify accessible route and provide compliant path or note exception.
RFI draft: Please confirm accessible route at service entrance per IBC Chapter 11.
Make-up air and kitchen exhaust balanceMechanical
High
Mechanical
Summary: Kitchen exhaust CFM and make-up air supply should be balanced per IMC; schedules not fully coordinated.
Why it matters: Imbalance can affect equipment operation and code compliance.
Suggested next step: Coordinate exhaust and make-up air on mechanical drawings.
RFI draft: Please confirm make-up air capacity matches kitchen exhaust per IMC.
Equipment schedule and plan tag consistencyFood Service
Medium
Food Service
Summary: Several equipment tags on plans do not match schedule numbering; some items skipped in sequence.
Why it matters: Inconsistency can cause procurement and installation errors.
Suggested next step: Align plan tags with equipment schedule and fill sequence gaps.
RFI draft: Please align equipment tags on plans with the equipment schedule.
Emergency power for critical kitchen loadsElectrical
Medium
Electrical
Summary: Critical refrigeration and cold storage may require emergency or optional standby power per code.
Why it matters: Loss of power can cause food safety and code issues.
Suggested next step: Confirm emergency/standby requirements and show on electrical design.
RFI draft: Please confirm if emergency or optional standby power is required for refrigeration.
Backflow prevention at hose connectionsPlumbing
Medium
Plumbing
Summary: Hose bibs and mop sinks in food service areas require appropriate backflow prevention per IPC.
Why it matters: Cross-connection risk to potable water system.
Suggested next step: Specify and detail backflow prevention at all hose connections.
RFI draft: Please confirm backflow prevention at hose bibs and mop sinks per IPC.
Egress width and door swingArchitectural
Medium
Architectural
Summary: One egress path may not meet minimum width with door swing in use.
Why it matters: Life safety and permit approval depend on egress compliance.
Suggested next step: Verify egress width with doors in use and revise if needed.
RFI draft: Please verify egress width with door swing per IBC.
Fire-rated penetrations at kitchen wallsFire Protection
Medium
Fire Protection
Summary: Duct and pipe penetrations at fire-rated kitchen walls need firestop details.
Why it matters: Unprotected penetrations compromise fire rating.
Suggested next step: Provide firestop details for all penetrations in rated assemblies.
RFI draft: Please provide firestop details for penetrations in fire-rated kitchen walls.
Ventilation rate for dining areaMechanical
Low
Mechanical
Summary: Outdoor air rate for dining area should be verified against IMC table.
Why it matters: Ensures acceptable IAQ and code compliance.
Suggested next step: Confirm ventilation rates on mechanical schedule.
RFI draft: Please confirm outdoor air rates for dining area per IMC.
Ground-fault protection for kitchen circuitsElectrical
Low
Electrical
Summary: Kitchen receptacles and equipment circuits require GFCI or other protection per NEC.
Why it matters: Safety and code compliance.
Suggested next step: Verify GFCI and protection requirements on electrical design.
RFI draft: Please confirm GFCI protection for kitchen circuits per NEC.
Floor drain slope and locationPlumbing
Low
Plumbing
Summary: Floor drain locations and slope to drain should be confirmed for kitchen and back-of-house.
Why it matters: Proper drainage prevents standing water and code issues.
Suggested next step: Verify floor drain layout and slope on plumbing and floor plans.
RFI draft: Please confirm floor drain locations and slope to drain.
This is an anonymized example. Findings shown are excerpts for illustration. Actual project details have been modified to protect client confidentiality.
Related case studies
Similar AI plan review results by project type and discipline.
- CommercialRetail Store Build-Out: 205 Issues Found in Commercial Construction205 issues · Fire Protection, Structural
- CommercialHotel Building Systems: 180 Issues Flagged180 issues · Landscape, Mechanical
- CommercialRestaurant Permit Set: 163 Issues Found163 issues · Architectural, Fire Protection
- CommercialCommercial Kitchen & Multi-Discipline Plan Review: 284 Issues Found284 issues · Architectural, Civil
- CommercialRetail Store Build-Out: 220 Issues Including Critical Egress, Fire Protection & Code Violations220 issues · Fire Protection, Structural
- CommercialCommercial Office Renovation: 906 Issues Found906 issues · Architectural, Electrical