Drawing Set Plan Review: 61 Issues Found

An anonymized drawing set plan review identified coordination and code issues before permit.

First $100 covered. Enterprise and volume pricing

Potential findings
61
Disciplines
5
Codes referenced
1
Critical or high examples shown
15

About this review

InspectMind ran an AI plan review on this project set and returned 61 potential findings across Architectural, Electrical, Mechanical, Plumbing, Structural. The selected examples below show the document conflict, why it matters, and a suggested next step.

Disciplines
Architectural, Electrical, Mechanical, Plumbing, Structural
Potential findings
61
Examples shown
15

Key findings

  1. Incorrect Applicable Plumbing and Mechanical Codes Referenced

    Plumbing

    Critical

    The plumbing notes explicitly direct all work to conform to the 2018 International Plumbing Code (IPC) and the International Mechanical Code (IMC). However, the 2022 California Building Code explicitly states that plumbing and mechanical systems are governed by the California Plumbing Code (CPC) and the California Mechanical Code (CMC).

  2. Incorrect Neutral Conductor Color Coding Specified in Notes

    Electrical

    Critical

    The general electrical notes explicitly specify that 'ALL NEUTRAL WIRES WILL BE BLACK IN COLOR' and 'UPS NEUTRAL WIRES WILL BE BLUE IN COLOR'. Section 2701.1 of the building code mandates that the California Electrical Code shall govern the design and installation of electrical components. Under California electrical standards, black and blue...

  3. No carbon monoxide detection shown on electrical plan for Group R occupancy alteration

    Electrical

    Critical

    The Electrical Symbol Key on sheet E002 defines detection symbols but only includes 'SD. SMOKE DETECTOR CEILING MOUNTED', no carbon monoxide (CO) detector symbol is listed. The electrical plan shows smoke detector hexagon symbols (SD.) in select rooms but no CO detection devices anywhere on the plan. Since smoke detectors are explicitly shown...

  4. Plumbing notes reference 2018 International Plumbing Code instead of required California Plumbing Code

    Plumbing

    Critical

    Plumbing Note 1 explicitly states all work shall conform to the '2018 INTERNATIONAL PLUMBING CODE.' Note 19 references support spacing 'IN ACCORDANCE WITH INTERNATIONAL PLUMBING CODE' and Note 21 requires pressure testing 'IN ACCORDANCE WITH THE IPC.' However, Section 302.2 of the 2022 California Existing Building Code requires that alterations...

  5. Plumbing notes reference 2018 International Plumbing Code instead of required 2022 California Plumbing Code

    Plumbing

    Critical

    The plumbing notes on sheet P001 repeatedly direct compliance with the wrong code. Note 1 states all work shall conform to the '2018 INTERNATIONAL PLUMBING CODE.' Note 19 directs support spacing 'IN ACCORDANCE WITH INTERNATIONAL PLUMBING CODE.' Note 21 directs pressure testing 'IN ACCORDANCE WITH THE IPC.' The applicable code for this...

  6. Plumbing Riser Detail specifies tubular 'S' traps, which cannot provide required siphonage protection

    Plumbing

    Critical

    The PLUMBING RAISER DETAIL explicitly labels '2'Ø WASTE PIPE WITH TUBULAR 'S' TRAP' at both the lavatory/sink and tub/shower fixture connections. An S-trap has a vertical outlet leg below the trap weir that inherently creates self-siphoning conditions during fixture drainage. The vertical drop acts as a siphon tube that pulls the water seal out...

  7. Hot Water Supply Branch Pipes Labeled Ø1/4' HWS: Below Minimum 1/2' Fixture Branch Size per Table 610.3

    Plumbing

    Critical

    The water supply plan consistently labels hot water supply (HWS) fixture branch pipes as Ø1/4' at multiple locations including kitchen sink, laundry room, and both bathrooms. Table 610.3 of the 2022 California Plumbing Code requires a minimum fixture branch pipe size of 1/2 inch for bathtubs, lavatories, kitchen sinks, and laundry sinks. The...

  8. Vent Pipe Labeled 'TO ROOM' Instead of Through Roof – Violates Roof Termination Requirement

    Plumbing

    Critical

    The sewerage line plan labels a Ø3' vent near the laundry/kitchen area as 'Ø3'VENT TO ROOM' while the other vents on the same plan are correctly labeled 'Ø2'VENT TO ROOF' (visible near the right-side bathroom serving Bedroom 01). Section 906.1 requires each vent pipe or stack to extend through its flashing and terminate vertically not less than...

  9. Non-Compliant PEX Flushing and Certification Procedure

    Plumbing

    Critical

    Plumbing Note 6 permits the use of PEX tubing for piping 1' and smaller. However, Plumbing Note 22 mandates that all potable water piping be flushed strictly per 'AMERICAN WATER WORKS ASSOCIATION STANDARDS'. This conflicts with the California Plumbing Code, which requires a specific 1-week standing flush, application of warning tags, and a...

  10. No Carbon Monoxide Alarms Shown on Electrical Plan Despite Attached Garage

    Electrical

    Critical

    The electrical plan shows an attached garage as part of the dwelling and notes exterior equipment labeled 'TANK LESS' (potentially a fuel-fired tankless water heater). However, the Electrical Symbol Key contains no carbon monoxide alarm symbol, and no CO alarm devices are depicted anywhere on the plan. Per R315.2.1, carbon monoxide alarms are...

Issue categories

Architectural
Egress, accessibility, room layouts, building code compliance, and finish specifications
Structural
Structural connections, load paths, foundation design, and structural code compliance
Electrical
Electrical systems, panelboards, circuits, and electrical code compliance
Mechanical
HVAC systems, ventilation, exhaust, and mechanical code compliance
Plumbing
Plumbing fixtures, drainage, venting, water supply, and plumbing code compliance

Review details and suggested questions

Incorrect Applicable Plumbing and Mechanical Codes Referenced

Plumbing

Critical

Summary: The plumbing notes explicitly direct all work to conform to the 2018 International Plumbing Code (IPC) and the International Mechanical Code (IMC). However, the 2022 California Building Code explicitly states that plumbing and mechanical systems are governed by the California Plumbing Code (CPC) and the California Mechanical Code (CMC).

Why it matters: Applying the IPC and IMC instead of California's state-adopted codes (the CPC and CMC) is a critical compliance failure. The California codes (which are based on the Uniform Plumbing Code and Uniform Mechanical Code) have fundamentally different methodologies and requirements for pipe sizing, venting layouts, fixture units, and approved...

Suggested next step: Please revise General Notes 1 and 26 to reference the currently adopted California Plumbing Code (CPC) and California Mechanical Code (CMC) in lieu of the IPC and IMC. Please also confirm that all pipe sizing, venting schemes, and system details have been designed in compliance with California requirements.

RFI draft: Please revise General Notes 1 and 26 to reference the currently adopted California Plumbing Code (CPC) and California Mechanical Code (CMC) in lieu of the IPC and IMC. Please also confirm that all pipe sizing, venting schemes, and system details have been designed in compliance with California...

Incorrect Neutral Conductor Color Coding Specified in Notes

Electrical

Critical

Summary: The general electrical notes explicitly specify that 'ALL NEUTRAL WIRES WILL BE BLACK IN COLOR' and 'UPS NEUTRAL WIRES WILL BE BLUE IN COLOR'. Section 2701.1 of the building code mandates that the California Electrical Code shall govern the design and installation of electrical components. Under California electrical standards, black and blue...

Why it matters: Using black for neutral wires creates a severe life-safety hazard. Electricians and maintenance personnel in the US universally identify black wires as energized (hot). If installed as specified in these notes, workers could be exposed to electrocution risks, and the installation will fail electrical inspections.

Suggested next step: Please revise the electrical general notes to align with the California Electrical Code. Specifically, designate white or gray for neutral conductors and reserve black, red, or blue for ungrounded (phase) conductors.

RFI draft: Please revise the electrical general notes to align with the California Electrical Code. Specifically, designate white or gray for neutral conductors and reserve black, red, or blue for ungrounded (phase) conductors.

No carbon monoxide detection shown on electrical plan for Group R occupancy alteration

Electrical

Critical

Summary: The Electrical Symbol Key on sheet E002 defines detection symbols but only includes 'SD. SMOKE DETECTOR CEILING MOUNTED', no carbon monoxide (CO) detector symbol is listed. The electrical plan shows smoke detector hexagon symbols (SD.) in select rooms but no CO detection devices anywhere on the plan. Since smoke detectors are explicitly shown...

Why it matters: This is a life-safety requirement. Failure to include CO detection would result in plan check rejection or inspection failure. The building includes an attached garage (a common CO source) and a 'TANK LESS' appliance noted on the exterior. Retroactively adding CO detection after construction would delay occupancy and incur additional cost for...

Suggested next step: Request the electrical engineer add carbon monoxide detection devices to the electrical plan and legend in accordance with Section 308.1 of the 2022 CEBC and the California Fire Code or CRC Section R315. Confirm device locations include all required areas per the applicable CO detection provisions (near sleeping areas, attached garage...

RFI draft: Request the electrical engineer add carbon monoxide detection devices to the electrical plan and legend in accordance with Section 308.1 of the 2022 CEBC and the California Fire Code or CRC Section R315. Confirm device locations include all required areas per the applicable CO detection...

Plumbing notes reference 2018 International Plumbing Code instead of required California Plumbing Code

Plumbing

Critical

Summary: Plumbing Note 1 explicitly states all work shall conform to the '2018 INTERNATIONAL PLUMBING CODE.' Note 19 references support spacing 'IN ACCORDANCE WITH INTERNATIONAL PLUMBING CODE' and Note 21 requires pressure testing 'IN ACCORDANCE WITH THE IPC.' However, Section 302.2 of the 2022 California Existing Building Code requires that alterations...

Why it matters: Designing and constructing to IPC requirements in a California jurisdiction will almost certainly result in plan check rejection by the Authority Having Jurisdiction. Pipe sizing, trap and vent sizing, and fixture unit calculations differ between the two codes, meaning the entire water supply and DWV design basis shown on this sheet may not...

Suggested next step: Request that the plumbing designer revise all plumbing notes (Notes 1, 19, 21, and any other references to the IPC) to reference the current California Plumbing Code (CPC) and confirm the entire plumbing design: including pipe sizing, venting, and testing requirements, complies with the CPC rather than the IPC.

RFI draft: Request that the plumbing designer revise all plumbing notes (Notes 1, 19, 21, and any other references to the IPC) to reference the current California Plumbing Code (CPC) and confirm the entire plumbing design: including pipe sizing, venting, and testing requirements, complies with the CPC rather...

Plumbing notes reference 2018 International Plumbing Code instead of required 2022 California Plumbing Code

Plumbing

Critical

Summary: The plumbing notes on sheet P001 repeatedly direct compliance with the wrong code. Note 1 states all work shall conform to the '2018 INTERNATIONAL PLUMBING CODE.' Note 19 directs support spacing 'IN ACCORDANCE WITH INTERNATIONAL PLUMBING CODE.' Note 21 directs pressure testing 'IN ACCORDANCE WITH THE IPC.' The applicable code for this...

Why it matters: Any California plan checker will reject drawings that reference the IPC instead of the CPC during plan review, causing immediate permit delay. If construction were to begin under IPC requirements before the discrepancy is caught, installations for pipe support spacing, pressure testing procedures, fixture provisions, and other elements may all...

Suggested next step: Request the plumbing designer revise all notes on sheet P001 to reference the 2022 California Plumbing Code instead of the 2018 International Plumbing Code. Specifically, revise Note 1 to cite the 2022 CPC as the governing code, revise Note 19 to reference CPC Table 313.3 for hanger and support spacing, and revise Note 21 to reference CPC...

RFI draft: Request the plumbing designer revise all notes on sheet P001 to reference the 2022 California Plumbing Code instead of the 2018 International Plumbing Code. Specifically, revise Note 1 to cite the 2022 CPC as the governing code, revise Note 19 to reference CPC Table 313.3 for hanger and support...

Plumbing Riser Detail specifies tubular 'S' traps, which cannot provide required siphonage protection

Plumbing

Critical

Summary: The PLUMBING RAISER DETAIL explicitly labels '2'Ø WASTE PIPE WITH TUBULAR 'S' TRAP' at both the lavatory/sink and tub/shower fixture connections. An S-trap has a vertical outlet leg below the trap weir that inherently creates self-siphoning conditions during fixture drainage. The vertical drop acts as a siphon tube that pulls the water seal out...

Why it matters: S-traps will be rejected during plan review by the Authority Having Jurisdiction. If constructed as detailed, the trap seals will self-siphon during normal use, allowing sewer gases (including hydrogen sulfide and methane) to enter the habitable spaces. This is a health and safety issue requiring redesign of the drainage connections for the...

Suggested next step: RFI to the plumbing designer: The PLUMBING RAISER DETAIL shows tubular 'S' traps at the lavatory/sink and tub/shower fixtures. S-traps cannot provide the siphonage protection required by CPC Section 901.2 and the trap seal protection required by Section 901.3. Please revise the detail to show P-traps with horizontal trap arms and proper vent...

RFI draft: RFI to the plumbing designer: The PLUMBING RAISER DETAIL shows tubular 'S' traps at the lavatory/sink and tub/shower fixtures. S-traps cannot provide the siphonage protection required by CPC Section 901.2 and the trap seal protection required by Section 901.3. Please revise the detail to show...

Hot Water Supply Branch Pipes Labeled Ø1/4' HWS: Below Minimum 1/2' Fixture Branch Size per Table 610.3

Plumbing

Critical

Summary: The water supply plan consistently labels hot water supply (HWS) fixture branch pipes as Ø1/4' at multiple locations including kitchen sink, laundry room, and both bathrooms. Table 610.3 of the 2022 California Plumbing Code requires a minimum fixture branch pipe size of 1/2 inch for bathtubs, lavatories, kitchen sinks, and laundry sinks. The...

Why it matters: Undersized 1/4' hot water supply branches would be rejected at plan check by the Authority Having Jurisdiction and would fail rough-in inspection if installed. The pipes would deliver severely inadequate flow to fixtures, and correcting them post-installation would require re-piping of all hot water branches throughout the building, resulting...

Suggested next step: Request the plumbing designer confirm and correct the hot water supply (HWS) fixture branch pipe sizes shown on the Water Supply Plan. Per Table 610.3, the minimum fixture branch pipe size for bathtubs, lavatories, kitchen sinks, and laundry sinks is 1/2 inch. All branches currently labeled Ø1/4' HWS should be revised to Ø1/2' HWS minimum,...

RFI draft: Request the plumbing designer confirm and correct the hot water supply (HWS) fixture branch pipe sizes shown on the Water Supply Plan. Per Table 610.3, the minimum fixture branch pipe size for bathtubs, lavatories, kitchen sinks, and laundry sinks is 1/2 inch. All branches currently labeled...

Vent Pipe Labeled 'TO ROOM' Instead of Through Roof – Violates Roof Termination Requirement

Plumbing

Critical

Summary: The sewerage line plan labels a Ø3' vent near the laundry/kitchen area as 'Ø3'VENT TO ROOM' while the other vents on the same plan are correctly labeled 'Ø2'VENT TO ROOF' (visible near the right-side bathroom serving Bedroom 01). Section 906.1 requires each vent pipe or stack to extend through its flashing and terminate vertically not less than...

Why it matters: If constructed as labeled, this vent would discharge sewer gases directly into the habitable space, creating a serious health and safety hazard. This will be flagged at plan review or inspection, causing a stop-work or correction order. The contractor would need to re-route the vent through the roof, potentially requiring structural...

Suggested next step: Request the plumbing designer clarify whether the label 'Ø3' VENT TO ROOM' near the laundry/kitchen area on the sewerage line plan is a drafting error and should read 'VENT TO ROOF' consistent with the other vents shown on the plan. Confirm the vent terminates through the roof per Section 906.1 and revise the drawing accordingly.

RFI draft: Request the plumbing designer clarify whether the label 'Ø3' VENT TO ROOM' near the laundry/kitchen area on the sewerage line plan is a drafting error and should read 'VENT TO ROOF' consistent with the other vents shown on the plan. Confirm the vent terminates through the roof per Section 906.1...

Non-Compliant PEX Flushing and Certification Procedure

Plumbing

Critical

Summary: Plumbing Note 6 permits the use of PEX tubing for piping 1' and smaller. However, Plumbing Note 22 mandates that all potable water piping be flushed strictly per 'AMERICAN WATER WORKS ASSOCIATION STANDARDS'. This conflicts with the California Plumbing Code, which requires a specific 1-week standing flush, application of warning tags, and a...

Why it matters: AWWA flushing standards do not satisfy California's strict PEX flushing and tagging protocols. The code explicitly states that the building official shall not give final permit approval unless the PEX installation complies with these specific CA flushing requirements. Specifying only AWWA standards will lead to non-compliant flushing...

Suggested next step: Please revise the plumbing notes to explicitly mandate the California-specific PEX flushing, tagging, and written certification requirements (including the 1-week standing flush) if PEX tubing is utilized, rather than solely referencing AWWA standards.

RFI draft: Please revise the plumbing notes to explicitly mandate the California-specific PEX flushing, tagging, and written certification requirements (including the 1-week standing flush) if PEX tubing is utilized, rather than solely referencing AWWA standards.

No Carbon Monoxide Alarms Shown on Electrical Plan Despite Attached Garage

Electrical

Critical

Summary: The electrical plan shows an attached garage as part of the dwelling and notes exterior equipment labeled 'TANK LESS' (potentially a fuel-fired tankless water heater). However, the Electrical Symbol Key contains no carbon monoxide alarm symbol, and no CO alarm devices are depicted anywhere on the plan. Per R315.2.1, carbon monoxide alarms are...

Why it matters: Failure to provide CO alarms where required is a life-safety violation that will be flagged during plan review and inspection, causing permit delays. CO alarm locations must be identified on the electrical plan to ensure proper installation during construction. This omission will require plan revision and resubmittal.

Suggested next step: Request the designer add carbon monoxide alarm locations to the electrical plan per R315.2.1, including a CO alarm symbol in the Electrical Symbol Key. Confirm whether the attached garage has an opening communicating with the dwelling unit and whether the tankless unit is fuel-fired, as both conditions independently trigger CO alarm...

RFI draft: Request the designer add carbon monoxide alarm locations to the electrical plan per R315.2.1, including a CO alarm symbol in the Electrical Symbol Key. Confirm whether the attached garage has an opening communicating with the dwelling unit and whether the tankless unit is fuel-fired, as both...

No Smoke Alarm Shown Inside Bedroom 01, R310.3 Requires Smoke Alarms in Each Sleeping Room

Electrical

Critical

Summary: The Main Floor Existing Electrical Plan documents smoke detector (SD) locations throughout the dwelling. The plan shows a ceiling-mounted smoke detector (SD) inside Bedroom 02, but no smoke detector symbol is shown inside Bedroom 01. The detailed view of Bedroom 01 shows four recessed lights, switches, and receptacles fully documented, yet no...

Why it matters: A missing smoke alarm in a sleeping room is a life-safety code violation that would result in inspection failure and a construction or occupancy delay. Per R310.2.2, where alterations, repairs, or additions requiring a permit occur, the individual dwelling unit shall be equipped with smoke alarms located as required for new dwellings. If the...

Suggested next step: Confirm whether a smoke alarm is intended to be installed inside Bedroom 01. If so, add an SD symbol inside Bedroom 01 on the proposed electrical plan and connect it to the smoke alarm circuit. Ensure the device is interconnected with the other smoke alarms in the dwelling unit as required by code.

RFI draft: Confirm whether a smoke alarm is intended to be installed inside Bedroom 01. If so, add an SD symbol inside Bedroom 01 on the proposed electrical plan and connect it to the smoke alarm circuit. Ensure the device is interconnected with the other smoke alarms in the dwelling unit as required by code.

Carbon Monoxide Alarms Missing from Electrical Plan for Dwelling with Attached Garage

Electrical

Critical

Summary: The electrical plan shows a dwelling with an attached GARAGE as part of the main floor layout and exterior equipment labeled 'TANK LESS' (commonly a gas tankless water heater, which would constitute a fuel-fired appliance). Per CRC R311.2.1, carbon monoxide alarms are required in dwelling units where the dwelling unit contains a fuel-fired...

Why it matters: Carbon monoxide alarms are a critical life-safety requirement under the California Residential Code. The complete absence of CO alarm symbols from the electrical legend and plan means these devices will not be roughed-in during electrical work, leading to plan check rejection or failed inspections. Per R311.3, CO alarms must be installed...

Suggested next step: Request that the designer add a carbon monoxide alarm symbol to the Electrical Symbol Key and show CO alarm locations on the electrical plan in compliance with CRC R311.2.1, R311.3, and R311.6. At minimum, CO alarms are required outside each separate sleeping area in the immediate vicinity of the bedrooms and on every occupiable level. Per...

RFI draft: Request that the designer add a carbon monoxide alarm symbol to the Electrical Symbol Key and show CO alarm locations on the electrical plan in compliance with CRC R311.2.1, R311.3, and R311.6. At minimum, CO alarms are required outside each separate sleeping area in the immediate vicinity of...

No bathroom mechanical exhaust ventilation shown on Mechanical Plan despite code requirement

Mechanical

Critical

Summary: The Mechanical Plan shows supply air diffusers (rectangle-with-X symbols) in multiple bathroom spaces (at least two rooms labeled 'BATH') but does not show any exhaust fan or wall exhaust grill symbols in any bathroom. The drawing legend explicitly defines both 'EXHAUST FAN' and 'WALL EXHAUST GRILL' symbols for use on this sheet, yet neither...

Why it matters: This omission will be identified during plan review and will result in permit rejection or a correction notice. Bathroom exhaust ventilation is a mandatory code requirement that cannot be waived. Failure to include exhaust fans and associated ductwork to the outdoors on the mechanical plan will delay permitting and require a plan revision....

Suggested next step: Request the mechanical designer to add exhaust fans in all bathrooms with ductwork routed to the outdoors, sized per California Mechanical Code Chapter 4 (minimum 50 CFM intermittent or 20 CFM continuous), as required by Section R325.2.1. Revise the mechanical plan to show exhaust fan locations, duct routing, termination points, and CFM ratings...

RFI draft: Request the mechanical designer to add exhaust fans in all bathrooms with ductwork routed to the outdoors, sized per California Mechanical Code Chapter 4 (minimum 50 CFM intermittent or 20 CFM continuous), as required by Section R325.2.1. Revise the mechanical plan to show exhaust fan locations,...

Bedroom 02 has no emergency escape and rescue opening shown on the existing floor plan

Architectural

Critical

Summary: The existing floor plan shows Bedroom 02 labeled as a sleeping room with interior dimensions of approximately 14'-8 3/4' x 13'-1 1/2'. No window, exterior door, or other opening to the exterior is depicted on any wall of Bedroom 02. The plan clearly shows window openings for adjacent rooms: the right exterior wall has two window-style openings,...

Why it matters: The absence of an emergency escape and rescue opening in a sleeping room is a critical life-safety deficiency. A plan reviewer will require that Bedroom 02 be provided with a compliant EERO meeting the minimum dimensions per Sections R319.2.1 through R319.2.3 (minimum 5.7 sq ft net clear opening, 24-inch minimum height, 20-inch minimum width,...

Suggested next step: Clarify how Bedroom 02 meets the emergency escape and rescue opening requirement per Section R319.1. If no compliant opening currently exists, provide a proposed solution (e.g., new window or exterior door) with dimensions confirming compliance with Sections R319.2.1 through R319.2.3, or re-designate the room as a non-sleeping use.

RFI draft: Clarify how Bedroom 02 meets the emergency escape and rescue opening requirement per Section R319.1. If no compliant opening currently exists, provide a proposed solution (e.g., new window or exterior door) with dimensions confirming compliance with Sections R319.2.1 through R319.2.3, or...

Missing Smoke Alarms Outside Sleeping Areas

Electrical

Critical

Summary: The electrical plans show 'SD.' (Smoke Detector) symbols inside the bedrooms ('PROPOSED BEDROOM', 'BEDROOM 01', and 'BEDROOM 02'). However, there are no smoke alarms shown in the 'PROPOSED HALLWAY' or the corridor areas immediately outside these bedrooms. The code mandates smoke alarms both inside and immediately outside each separate sleeping...

Why it matters: Providing smoke alarms inside bedrooms without placing them in the immediate vicinity outside the sleeping areas violates fundamental egress and life-safety code requirements. Alarms outside bedrooms provide critical early warning for fires starting in other areas of the house.

Suggested next step: Please add smoke detectors to the floor plan in the hallway/corridor immediately outside 'PROPOSED BEDROOM', 'BEDROOM 01', and 'BEDROOM 02' to satisfy code location requirements.

RFI draft: Please add smoke detectors to the floor plan in the hallway/corridor immediately outside 'PROPOSED BEDROOM', 'BEDROOM 01', and 'BEDROOM 02' to satisfy code location requirements.

This is an anonymized example. Findings shown are excerpts for illustration. Actual project details have been modified to protect client confidentiality.