Back to Case Studies
Manufactured HomeCaliforniaSDC D

26 Issues Found Including Critical Seismic Anchorage & Accessibility Violations

Wood pad foundations in Seismic Design Category D, no accessible route to entrances, and incorrect HUD pre-emption claims—surfaced before permit submission.

26
Issues Found
SDC D
Seismic Category
4
Critical Issues

The Project

A manufactured/prefab ADU project in California located in Seismic Design Category D. InspectMind reviewed the drawing set and identified critical deficiencies in seismic anchorage, fundamental accessibility violations, incorrect claims about HUD pre-emption of California codes, and extensive document coordination errors between floor plans, elevations, and site plans—issues that would have caused immediate permit rejection and potentially dangerous construction.

2022 CA Building CodeCBC 1604.4AISC 341CBC Chapter 11

Sample Findings

CriticalWood Pad Foundations in SDC D

Foundation uses wood pads on ground with 1/4" self-tapping screws. SDC D requires positive mechanical anchorage per CBC 1604.4 and AISC 341—structure could slide off foundation in earthquake.

CriticalUnstable Three-Point Landing Support

Free-standing landing supported by only three 4x4 posts with non-moment-resisting bases. A rectangular assembly on three points is geometrically unstable under lateral loads.

CriticalLocation Map and Site Plan Show Different Properties

Location map shows one urban block location. Site plan shows property at a completely different location with different neighboring parcels—two entirely different geographical sites.

HighNo Accessible Route to Either Entrance

Both entrances accessed via stairs only. CBC Section 1117A.3 requires ground-floor units to have accessible routes—steps are prohibited on accessible paths.

HighIncorrect HUD Pre-emption Claim

Notes claim "ALL MH PRE-EMPT CALIFORNIA REQUIREMENTS." HUD pre-empts unit construction only—site installation, fire protection, and accessibility still follow CBC per Section 420.1.

HighSprinkler Requirement Contradiction

"ADU WILL NOT HAVE SPRINKLERS" contradicts CBC 903.2 and conflicts with scope noting "water tank for fire suppression system."

Issue Categories

Structural & Seismic

SDC D anchorage, unstable supports, missing member sizes

Accessibility

No accessible routes, 8" thresholds, stairs at all entries

Document Coordination

Floor plan/elevation conflicts, location map errors, generic plans

Code Compliance

HUD pre-emption errors, sprinkler contradictions, concrete strength

Value Delivered

26 issues surfaced before permit submission
Critical SDC D anchorage deficiency identified
California accessibility violations flagged
HUD vs CBC jurisdiction clarified

"The seismic anchorage issue alone could have resulted in a dangerous installation. Having an AI catch these fundamental issues before permit submission saved us from both liability and costly redesign."

— Project Team