New Orleans Urban Infill: 11 Issues Found
Anonymized historic urban infill; code and coordination issues before city review.
Free check on up to 10 drawing pages. Enterprise and volume pricing
- 1Critical · GeneralDrawing Index Audit: 1 missing, 0 mismatched, 0 minor mismatches out of 12 indexed pages
- 2Critical · GeneralR-2 Occupancy Explicitly States No Automatic Sprinkler System, Violating Section 420.4
- 3Critical · ArchitecturalExterior Exit Stairways Do Not Meet 10-Foot Minimum Fire Separation Distance to Property Line
Fig. 1 · Top findings, pinned on the set
- Potential findings
- 11
- Disciplines
- 2
- Codes referenced
- 1
- Critical or high examples shown
- 8
Checkers used on this project
Run the same check on your set →About this review
InspectMind ran an AI plan review on this project set and returned 11 potential findings across Architectural, General. The selected examples below show the document conflict, why it matters, and a suggested next step.
- Disciplines
- Architectural, General
- Potential findings
- 11
- Examples shown
- 11
Key findings
- 1Critical
Drawing Index Audit: 1 missing, 0 mismatched, 0 minor mismatches out of 12 indexed pages
General
12 indexed pages | 11 match | 0 minor mismatch | 0 mismatch | 1 missing Missing (1), listed in drawing index but not found in the document: Architectural: - A6.2 DOOR & WINDOW SCHEDULES
- 2Critical
R-2 Occupancy Explicitly States No Automatic Sprinkler System, Violating Section 420.4
General · IBC
The Zoning/Code Information on the title sheet identifies the building occupancy as R-2 Residential and explicitly states 'SPRINKLERED / FIRE ALARM: NO / NO.' Section 420.4 of the 2021 IBC mandates that 'Group R occupancies shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.2.8.' The drawing's...
- 3Critical
Exterior Exit Stairways Do Not Meet 10-Foot Minimum Fire Separation Distance to Property Line
Architectural
The 1st Floor Life Safety Plan shows multiple exterior exit stairways serving as required means of egress components. On the west side, a 56' exterior stair is located adjacent to the building face, and the 2nd Floor Life Safety Plan dimensions the distance from the property line to the dwelling wall at only 3'-9' on that same west side. On the...
- 4Critical
Alteration Level misclassified as Level 2 when scope of work equals 100% of building area, requiring Level 3
Architectural · IBC
The drawing states the building square footage is 5,766 SF and the scope of work square footage is also 5,766 SF, meaning the work area encompasses 100% of the building area. However, the drawing classifies the SFM Level of Alteration as Level 2 (≤ 50% VALUE OF BUILDING). Per IEBC Section 603.1, Level 2 alterations apply only where the work...
- 5High
Fire Extinguishers Shown as Class A Only (F-A); IBC 906.1 Requires Minimum 1-A:10-B:C Rating for R-2 Dwelling Units
General · IBC
The NFPA Legend defines the F-A symbol as 'CLASS A EXTINGUISHERS WILL PUT OUT FIRES IN ORDINARY COMBUSTIBLES SUCH AS WOOD AND PAPER' and separately defines F-B as 'CLASS B EXTINGUISHERS ARE FOR USE ON FLAMMABLE LIQUIDS LIKE GREASE, GASOLINE & OIL,' confirming these are distinct, single-class extinguisher types. Both the 1st Floor and 2nd Floor...
- 6High
Rear stairwell switchback stair cannot achieve required 80' headroom with 12'-10' floor-to-floor height
Architectural
Section 3 (PROPOSED REAR STAIRWELL SECTION) on sheet A4.1 shows a switchback stair with a floor-to-floor height of 12'-10' (154') from B.F.E. REQ. (0'-0') to 2ND FLOOR (12'-10'), with 22 equal treads and 7' TYP. riser heights. With 22 risers at 7' each (22 × 7' = 154'), this confirms the total rise. In a switchback configuration with...
- 7High
Ceiling Detail C-0.3: 1x4 Furring Strips Below Minimum 2' Nominal Thickness Required for Gypsum Board Support
Architectural
Detail C-0.3 (CEILING ASSEMBLY - WOOD JOIST) specifies '1x4 FURRING STRIPS RUNNING PERPENDICULAR TO JOIST FRAMING @ 24' O.C. FOR SHEETROCK ATTACHMENT' supporting '1/2' GYPSUM BOARD.' The 1x4 furring strips have a nominal least dimension of 1 inch, which is less than the 2-inch nominal minimum required by IBC Section 2504.1.1. The exception...
- 8High
Exterior Trim Material Conflict: Drawing Specifies Solid Wood Trim vs. Spec Requires Cementitious Fiber Board Trim
Architectural
Drawing keynote N-19 specifies that 'ALL NEW TRIM AND CORNER-BOARDS TO BE TREATED SOLID WOOD TO MATCH EXISTING,' while the project specification under Exterior Finishes states 'WALLS & TRIM - CEMENTITIOUS FIBER BOARD TRIM & SIDING.' The drawing calls for treated solid wood for all new trim and corner-boards, directly contradicting the...
- 9Medium
Exterior Fire-Rated Wall EF-1.1: Gypsum Board Type Not Specified as Type X for 1-Hour Fire-Rated Assembly
Architectural
Detail EF-1.1 is designated as a '(1 HOUR RATED)' exterior wall assembly referencing 'UL U303,' but specifies only '5/8' GYPSUM BOARD' without indicating the required fire-rated gypsum board type (e.g., Type X). IBC Section 2502.1 requires that gypsum board construction, where required for fire protection, shall comply with the provisions of...
- 10Medium
Roof/attic insulation type conflict: Keynote N-01 specifies batt insulation while assembly R-1.1 specifies spray foam
Architectural
On sheet A4.1 (Building Sections), keynote N-01, tagged at the roof assembly in the building sections, states 'BATT INSULATION AT ATTIC CEILING' for the new architectural shingle roof. However, on sheet A6.1 (Vertical & Horizontal Assemblies), the roof assembly R-1.1 titled 'ROOF ASSEMBLY - SHINGLE W/ SPRAY INSULATION' specifies 'SPRAY FOAM...
Issue categories
- Cat. 01Architectural
- Egress, accessibility, room layouts, building code compliance, and finish specifications
- Cat. 02General
- Drawing index, coordination, and general plan review findings
Review details and suggested questions
01Drawing Index Audit: 1 missing, 0 mismatched, 0 minor mismatches out of 12 indexed pagesGeneral
Critical
General
Summary: 12 indexed pages | 11 match | 0 minor mismatch | 0 mismatch | 1 missing Missing (1), listed in drawing index but not found in the document: Architectural: - A6.2 DOOR & WINDOW SCHEDULES
Why it matters:
Suggested next step:
RFI draft: 📄 A1.0 Schedule Text: DRAWING INDEX, page 1
02R-2 Occupancy Explicitly States No Automatic Sprinkler System, Violating Section 420.4General · IBC
Critical
General · IBC
Summary: The Zoning/Code Information on the title sheet identifies the building occupancy as R-2 Residential and explicitly states 'SPRINKLERED / FIRE ALARM: NO / NO.' Section 420.4 of the 2021 IBC mandates that 'Group R occupancies shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.2.8.' The drawing's...
Why it matters: This is a fundamental life-safety and code compliance conflict that will be flagged during Louisiana State Fire Marshal review for permitting. The absence of a required automatic sprinkler system in an 8-unit, 2-story, Type V-B (unprotected combustible) apartment building represents a significant fire and life-safety deficiency. This will...
Suggested next step: Request the design team to clarify the basis for stating no sprinkler system is provided for this R-2 occupancy. If the project is relying on the 2021 International Existing Building Code (IEBC) for an exemption under Level 2 alterations, this basis must be explicitly documented on the drawings with the specific IEBC section cited. If no valid...
RFI draft: Request the design team to clarify the basis for stating no sprinkler system is provided for this R-2 occupancy. If the project is relying on the 2021 International Existing Building Code (IEBC) for an exemption under Level 2 alterations, this basis must be explicitly documented on the drawings...
03Exterior Exit Stairways Do Not Meet 10-Foot Minimum Fire Separation Distance to Property LineArchitectural
Critical
Architectural
Summary: The 1st Floor Life Safety Plan shows multiple exterior exit stairways serving as required means of egress components. On the west side, a 56' exterior stair is located adjacent to the building face, and the 2nd Floor Life Safety Plan dimensions the distance from the property line to the dwelling wall at only 3'-9' on that same west side. On the...
Why it matters: Non-compliance with the 10-foot fire separation distance requirement for exterior exit stairways is a fundamental site-layout and code compliance issue that the Louisiana State Fire Marshal will likely identify during plan review for permitting. Corrective measures could require relocating the exterior stairs, adjusting the building footprint,...
Suggested next step: Request the architect to verify and dimension the fire separation distance from the exterior edge of each exterior exit stairway (including landings) to the adjacent property line and confirm compliance with IBC Section 1027.5. If the distances are confirmed to be less than 10 feet, request a revised egress design or alternate compliance path.
RFI draft: Request the architect to verify and dimension the fire separation distance from the exterior edge of each exterior exit stairway (including landings) to the adjacent property line and confirm compliance with IBC Section 1027.5. If the distances are confirmed to be less than 10 feet, request a...
04Alteration Level misclassified as Level 2 when scope of work equals 100% of building area, requiring Level 3Architectural · IBC
Critical
Architectural · IBC
Summary: The drawing states the building square footage is 5,766 SF and the scope of work square footage is also 5,766 SF, meaning the work area encompasses 100% of the building area. However, the drawing classifies the SFM Level of Alteration as Level 2 (≤ 50% VALUE OF BUILDING). Per IEBC Section 603.1, Level 2 alterations apply only where the work...
Why it matters: Incorrect classification as Level 2 instead of Level 3 means the project is not being designed to comply with the additional requirements of Chapter 9 (Level 3 alterations), which per Section 604.2 requires compliance with Chapters 7, 8, AND 9. Chapter 9 imposes more stringent requirements for fire protection, means of egress, and other...
Suggested next step: Request the design team to clarify the work area calculation and confirm whether the work area exceeds 50% of the building area per IEBC Section 603.1 and 604.1. If the scope of work square footage (5,766 SF) is indeed the work area and equals the total building area (5,766 SF), the project must be reclassified as a Level 3 alteration and...
RFI draft: Request the design team to clarify the work area calculation and confirm whether the work area exceeds 50% of the building area per IEBC Section 603.1 and 604.1. If the scope of work square footage (5,766 SF) is indeed the work area and equals the total building area (5,766 SF), the project must...
05Fire Extinguishers Shown as Class A Only (F-A); IBC 906.1 Requires Minimum 1-A:10-B:C Rating for R-2 Dwelling UnitsGeneral · IBC
High
General · IBC
Summary: The NFPA Legend defines the F-A symbol as 'CLASS A EXTINGUISHERS WILL PUT OUT FIRES IN ORDINARY COMBUSTIBLES SUCH AS WOOD AND PAPER' and separately defines F-B as 'CLASS B EXTINGUISHERS ARE FOR USE ON FLAMMABLE LIQUIDS LIKE GREASE, GASOLINE & OIL,' confirming these are distinct, single-class extinguisher types. Both the 1st Floor and 2nd Floor...
Why it matters: During Louisiana State Fire Marshal permitting review, the conflict between the legend/plan symbols (Class A only) and the IBC Section 906.1 minimum rating (1-A:10-B:C) would be flagged. If a contractor installs Class A-only extinguishers per the legend and plan symbols, the installation would fail fire inspection, causing construction delays...
Suggested next step: Clarify the fire extinguisher specification on the life safety plans. Revise the NFPA Legend to show that all dwelling unit extinguishers shall be multi-rated ABC type with a minimum rating of 2A-10B-C as stated in General Note 1 and consistent with IBC Section 906.1 Exception 1 for R-2 occupancies. Update or replace the F-A symbol and...
RFI draft: Clarify the fire extinguisher specification on the life safety plans. Revise the NFPA Legend to show that all dwelling unit extinguishers shall be multi-rated ABC type with a minimum rating of 2A-10B-C as stated in General Note 1 and consistent with IBC Section 906.1 Exception 1 for R-2...
06Rear stairwell switchback stair cannot achieve required 80' headroom with 12'-10' floor-to-floor heightArchitectural
High
Architectural
Summary: Section 3 (PROPOSED REAR STAIRWELL SECTION) on sheet A4.1 shows a switchback stair with a floor-to-floor height of 12'-10' (154') from B.F.E. REQ. (0'-0') to 2ND FLOOR (12'-10'), with 22 equal treads and 7' TYP. riser heights. With 22 risers at 7' each (22 × 7' = 154'), this confirms the total rise. In a switchback configuration with...
Why it matters: Insufficient stair headroom is a life-safety issue that would be identified during Louisiana State Fire Marshal plan review and would result in rejection of the permit application. During construction, this would require a costly redesign of the stairwell: potentially involving changes to landing positions, floor openings, or conversion to a...
Suggested next step: Request the architect to verify stair headroom clearance throughout the rear stairwell switchback stair per Section 1011.3 (80' minimum). With the 12'-10' floor-to-floor height and equal switchback flights, demonstrate how 80' headroom is achieved at all points along the stair, including under the upper flight. If compliant headroom cannot be...
RFI draft: Request the architect to verify stair headroom clearance throughout the rear stairwell switchback stair per Section 1011.3 (80' minimum). With the 12'-10' floor-to-floor height and equal switchback flights, demonstrate how 80' headroom is achieved at all points along the stair, including under...
07Ceiling Detail C-0.3: 1x4 Furring Strips Below Minimum 2' Nominal Thickness Required for Gypsum Board SupportArchitectural
High
Architectural
Summary: Detail C-0.3 (CEILING ASSEMBLY - WOOD JOIST) specifies '1x4 FURRING STRIPS RUNNING PERPENDICULAR TO JOIST FRAMING @ 24' O.C. FOR SHEETROCK ATTACHMENT' supporting '1/2' GYPSUM BOARD.' The 1x4 furring strips have a nominal least dimension of 1 inch, which is less than the 2-inch nominal minimum required by IBC Section 2504.1.1. The exception...
Why it matters: Using undersized furring strips for ceiling gypsum board attachment could result in inadequate support, leading to ceiling deflection, cracking, or failure. This would be flagged during plan review by the Louisiana State Fire Marshal's office and building inspections. Correction during construction would require removal and replacement of all...
Suggested next step: Request the design team to revise Detail C-0.3 to specify minimum 2x4 wood furring (2-inch nominal thickness in the least dimension) in lieu of 1x4 furring strips, or provide an alternative ceiling support system that complies with IBC Section 2504.1.1.
RFI draft: Request the design team to revise Detail C-0.3 to specify minimum 2x4 wood furring (2-inch nominal thickness in the least dimension) in lieu of 1x4 furring strips, or provide an alternative ceiling support system that complies with IBC Section 2504.1.1.
08Exterior Trim Material Conflict: Drawing Specifies Solid Wood Trim vs. Spec Requires Cementitious Fiber Board TrimArchitectural
High
Architectural
Summary: Drawing keynote N-19 specifies that 'ALL NEW TRIM AND CORNER-BOARDS TO BE TREATED SOLID WOOD TO MATCH EXISTING,' while the project specification under Exterior Finishes states 'WALLS & TRIM - CEMENTITIOUS FIBER BOARD TRIM & SIDING.' The drawing calls for treated solid wood for all new trim and corner-boards, directly contradicting the...
Why it matters: This material conflict could impact HDLC approval since the drawing's intent is to match existing historic wood trim, while the spec mandates a different material. Using the wrong material may lead to rejection by the historic preservation commission or require costly replacement after installation. Additionally, cementitious fiber board and...
Suggested next step: Request clarification on the intended exterior trim and corner-board material. The drawing keynote N-19 calls for treated solid wood to match existing, while the specification requires cementitious fiber board. Confirm which material should be used, considering HDLC/historic preservation requirements, and revise the conflicting document...
RFI draft: Request clarification on the intended exterior trim and corner-board material. The drawing keynote N-19 calls for treated solid wood to match existing, while the specification requires cementitious fiber board. Confirm which material should be used, considering HDLC/historic preservation...
09Exterior Fire-Rated Wall EF-1.1: Gypsum Board Type Not Specified as Type X for 1-Hour Fire-Rated AssemblyArchitectural
Medium
Architectural
Summary: Detail EF-1.1 is designated as a '(1 HOUR RATED)' exterior wall assembly referencing 'UL U303,' but specifies only '5/8' GYPSUM BOARD' without indicating the required fire-rated gypsum board type (e.g., Type X). IBC Section 2502.1 requires that gypsum board construction, where required for fire protection, shall comply with the provisions of...
Why it matters: Not specifying the fire-rated gypsum board type (Type X) for a 1-hour rated assembly could result in installation of standard 5/8-inch gypsum board, which does not provide equivalent fire resistance. This would likely be flagged during Louisiana State Fire Marshal plan review for permitting, causing delays. If standard gypsum is installed...
Suggested next step: Request the design team to clarify the gypsum board specification for wall type EF-1.1 to include the specific fire-rated type (e.g., 5/8' Type X or Type C) as required by UL U303 for the 1-hour fire rating, consistent with the approach used for interior fire-rated wall IF-1.1.
RFI draft: Request the design team to clarify the gypsum board specification for wall type EF-1.1 to include the specific fire-rated type (e.g., 5/8' Type X or Type C) as required by UL U303 for the 1-hour fire rating, consistent with the approach used for interior fire-rated wall IF-1.1.
10Roof/attic insulation type conflict: Keynote N-01 specifies batt insulation while assembly R-1.1 specifies spray foamArchitectural
Medium
Architectural
Summary: On sheet A4.1 (Building Sections), keynote N-01, tagged at the roof assembly in the building sections, states 'BATT INSULATION AT ATTIC CEILING' for the new architectural shingle roof. However, on sheet A6.1 (Vertical & Horizontal Assemblies), the roof assembly R-1.1 titled 'ROOF ASSEMBLY - SHINGLE W/ SPRAY INSULATION' specifies 'SPRAY FOAM...
Why it matters: This conflict creates ambiguity about whether the attic is intended to be conditioned (spray foam at rafters per R-1.1 and N-31) or unconditioned (batt insulation at the ceiling plane per N-01). The correct insulation strategy directly affects IECC energy code compliance, moisture management, MEP equipment placement within the attic, and...
Suggested next step: Please clarify the intended attic insulation strategy: Is the attic to be conditioned with spray foam insulation at the rafters (per assembly R-1.1 on A6.1 and keynote N-31 on A4.1), or unconditioned with batt insulation at the attic ceiling (per keynote N-01 on A4.1)? Please revise the conflicting keynote or assembly detail to ensure a...
RFI draft: Please clarify the intended attic insulation strategy: Is the attic to be conditioned with spray foam insulation at the rafters (per assembly R-1.1 on A6.1 and keynote N-31 on A4.1), or unconditioned with batt insulation at the attic ceiling (per keynote N-01 on A4.1)? Please revise the...
11Exterior wall section uses batt insulation hatch instead of specified open-cell spray foamArchitectural
Medium
Architectural
Summary: The exterior wall cavity in the latitudinal building section is drawn with the batt-insulation hatch identified in the legend. The specification requires open-cell spray polyurethane foam between exterior studs at R-13, so the wall assembly shown on this page contradicts the specified insulation type.
Why it matters: If this remains uncorrected, bidders and installers may carry the wrong wall insulation system, affecting envelope performance and creating inconsistency between the approved drawings and the specification.
Suggested next step: Please confirm the required exterior wall insulation. Should the section be revised to show open-cell spray polyurethane foam between exterior studs at R-13 per the specification, or is a specification revision intended?
RFI draft: Please confirm the required exterior wall insulation. Should the section be revised to show open-cell spray polyurethane foam between exterior studs at R-13 per the specification, or is a specification revision intended?
This case study uses anonymized project data. Details are generalized for confidentiality. Findings illustrate the type of issues InspectMind surfaces before permit or construction.
Related case studies
Similar AI plan review results by project type and discipline.
- CommercialPlan Review: 29 Issues Found29issues · Architectural, General
- CommercialPlan Review: 26 Issues Found26issues · Architectural, General
- CommercialPlan Review: 25 Issues Found25issues · Architectural, General
- CommercialPlan Review: 25 Issues Found25issues · Architectural, General
- CommercialFinal Redline Set: 24 Issues Found24issues · Architectural, Electrical
- CommercialPlan Review: 23 Issues Found23issues · Architectural, General