Electrical Substation Replacement: 238 Issues Flagged
Check transfer-switch configuration, protective functions, and control destinations in a 90-percent electrical set.
Enterprise & volume pricing
Anonymized review · Published 2026-09-16
What this review documents
Check transfer-switch configuration, protective functions, and control destinations in a 90-percent electrical set.
The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.
Key findings
Three-pole transfer switch is scheduled with a switched neutral
Electrical
The schedule pairs a three-pole transfer switch with a switched neutral, while the specification assigns switched neutrals to four-pole units.
Next step: Confirm the grounding arrangement and intended transfer-switch pole configuration.
Main-breaker trip function differs from specification
Electrical
An 800-ampere main breaker is labeled with LSI protection. The specification also requires a ground-fault function or alarm for the applicable device class.
Next step: Verify applicability and coordinate the protection and alarm requirements.
Monitoring connection points to a different control panel
Electrical / IT/Communications
The drawing routes a transfer-switch monitoring connection to a different remote control panel than the specification identifies.
Next step: Reconcile the control destination and update wiring and point schedules.
Issue categories
Review details and suggested questions
Three-pole transfer switch is scheduled with a switched neutralElectricalHigh
Summary: The schedule pairs a three-pole transfer switch with a switched neutral, while the specification assigns switched neutrals to four-pole units.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Confirm the grounding arrangement and intended transfer-switch pole configuration.
RFI draft: Confirm the grounding arrangement and intended transfer-switch pole configuration.
Main-breaker trip function differs from specificationElectricalHigh
Summary: An 800-ampere main breaker is labeled with LSI protection. The specification also requires a ground-fault function or alarm for the applicable device class.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Verify applicability and coordinate the protection and alarm requirements.
RFI draft: Verify applicability and coordinate the protection and alarm requirements.
Monitoring connection points to a different control panelElectrical / IT/CommunicationsHigh
Summary: The drawing routes a transfer-switch monitoring connection to a different remote control panel than the specification identifies.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Reconcile the control destination and update wiring and point schedules.
RFI draft: Reconcile the control destination and update wiring and point schedules.
Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.
Related case studies
Similar AI plan review results by project type and discipline. Browse all case studies
Want this on your next set?
Start with the first $100 covered. See cited issues in hours, no call required.
- Evidence-linked findings
- 5+ issues or full refund
- Results in hours
5+ issues or full refund · No demo required