An anonymized Wichita site/commercial plan review uncovered coordination and code issues—before permit.

102
Potential findings
8
Disciplines
2
Codes referenced
Start with $100 creditSee the findings

Enterprise & volume pricing

Key findings

Drawing Index Audit: 4 missing, 32 mismatched out of 58 sheets

General

Critical

58 index entries | 22 perfect matches | 32 mismatched | 4 missing Mismatched (32): CS: Expected: COVER SHEET (CS) | Actual: COVER SHEET (MP0.1)(p73) A1.1: Expected: ARCHITECTURAL SITE PLAN (A1.1) | Actual: site plan (A1.1)(p18) A2.1: Expected: OVERALL BASEMENT PLAN (A2.1) | Actual: floor plan (A2.1)(p19) A2.2: ...

Reinforcement Invalidated by Estimating Purpose Note

Structural

Critical

The general structural notes state that 'CONCRETE REINFORCING BARS SHOWN SHALL BE USED FOR ESTIMATING PURPOSES ONLY.' However, ACI 318-19 Section 26.6.1.1 mandates that the construction documents must explicitly provide the type, size, location, detailing, and embedment length of reinforcement as definitive design information. By marking the...

Insufficient longitudinal reinforcement in concrete columns CC1 and CC2

Structural

Critical

ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement in columns to be at least 0.01Ag (1% of the gross concrete area). The Structural Column Schedule specifies column CC1 as 24' x 24' (Ag = 576 sq in) and column CC2 as 12' x 24' (Ag = 288 sq in). Both are scheduled with '#6 BARS EA CORNER' (4 bars total). The area of four...

Insufficient Longitudinal Reinforcement Area in Concrete Columns CC1 and CC2

Structural

Critical

ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement in nonprestressed columns to be at least 0.01Ag. The Structural Column Schedule specifies concrete column CC1 as '24' x 24' w/ #6 BARS EA CORNER' and CC2 as '12' x 24' w/ #6 BARS EA CORNER'. Providing only four #6 bars (one at each corner) yields a total steel area of...

Columns CC1 and CC2 have insufficient longitudinal reinforcement area

Structural

Critical

The Structural Column Schedule details concrete column CC1 as '24' x 24' w/ #6 BARS EA CORNER' (gross area Ag = 576 in²) and CC2 as '12' x 24' w/ #6 BARS EA CORNER' (gross area Ag = 288 in²). Assuming one bar per corner, this provides 4 #6 bars total per column, yielding a steel area (As) of approximately 1.76 in². ACI 318-19 Section 10.6.1.1...

Concrete columns CC1 and CC2 lack minimum required longitudinal reinforcement

Structural

Critical

According to ACI 318-19 Section 10.6.1.1, the area of longitudinal reinforcement for columns must be at least 0.01Ag (1% of the gross concrete area). The Structural Concrete Column Schedule specifies column CC1 as '24' x 24' w/ #6 BARS EA CORNER'. A 24' x 24' column has a gross area (Ag) of 576 sq in, requiring a minimum of 5.76 sq in of...

Concrete Columns CC1 and CC2 Lack Minimum Longitudinal Reinforcement

Structural

Critical

The Structural Column Schedule specifies concrete column CC1 (24' x 24') and CC2 (12' x 24') to be reinforced with '#6 BARS EA CORNER' (4 bars total). ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement to be at least 0.01Ag (1% of the gross cross-sectional area). For CC1, the minimum reinforcement is 5.76 sq in (0.01 ×...

Concrete Columns CC1 and CC2 violate minimum longitudinal reinforcement ratio (0.01Ag)

Structural

Critical

The Structural Column Schedule details column CC1 as 24' x 24' (Gross Area Ag = 576 sq in) and column CC2 as 12' x 24' (Gross Area Ag = 288 sq in). Both are scheduled with '#6 BARS EA CORNER', which equates to 4 total #6 bars. The area of four #6 bars is approximately 1.76 sq in. ACI 318-19 Section 10.6.1.1 requires longitudinal reinforcement...

Insufficient minimum longitudinal reinforcement in concrete columns CC1 and CC2

Structural

Critical

The Structural Column Schedule details concrete column CC1 as 24' x 24' (gross area Ag = 576 sq in) and CC2 as 12' x 24' (gross area Ag = 288 sq in). Both columns are scheduled with '#6 BARS EA CORNER', providing exactly 4 #6 bars (total area As = 1.76 sq in). This results in a longitudinal reinforcement ratio of approximately 0.003 for CC1 and...

Insufficient longitudinal reinforcement area for concrete columns CC1 and CC2

Structural

Critical

The Structural Column Schedule specifies concrete column CC1 as 24' x 24' (Ag = 576 sq in) and CC2 as 12' x 24' (Ag = 288 sq in). Both are reinforced with '#6 BARS EA CORNER', which equates to 4 #6 bars per column (totaling approximately 1.76 sq in of steel). ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement to be at...

Issue categories

Architectural
Egress, accessibility, room layouts, building code compliance, and finish specifications
Structural
Structural connections, load paths, foundation design, and structural code compliance
Electrical
Electrical systems, panelboards, circuits, and electrical code compliance
Mechanical
HVAC systems, ventilation, exhaust, and mechanical code compliance
Plumbing
Plumbing fixtures, drainage, venting, water supply, and plumbing code compliance
Civil
Site grading, utilities, stormwater, and civil coordination
Landscape
Landscape and site improvement coordination
General
Drawing index, coordination, and general plan review findings

Review details and suggested questions

Drawing Index Audit: 4 missing, 32 mismatched out of 58 sheets
General
Critical

Summary: 58 index entries | 22 perfect matches | 32 mismatched | 4 missing Mismatched (32): CS: Expected: COVER SHEET (CS) | Actual: COVER SHEET (MP0.1)(p73) A1.1: Expected: ARCHITECTURAL SITE PLAN (A1.1) | Actual: site plan (A1.1)(p18) A2.1: Expected: OVERALL BASEMENT PLAN (A2.1) | Actual: floor plan (A2.1)(p19) A2.2: ...

Why it matters:

Suggested next step:

RFI draft:

Reinforcement Invalidated by Estimating Purpose Note
Structural
Critical

Summary: The general structural notes state that 'CONCRETE REINFORCING BARS SHOWN SHALL BE USED FOR ESTIMATING PURPOSES ONLY.' However, ACI 318-19 Section 26.6.1.1 mandates that the construction documents must explicitly provide the type, size, location, detailing, and embedment length of reinforcement as definitive design information. By marking the...

Why it matters:

Suggested next step:

RFI draft:

Insufficient longitudinal reinforcement in concrete columns CC1 and CC2
Structural
Critical

Summary: ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement in columns to be at least 0.01Ag (1% of the gross concrete area). The Structural Column Schedule specifies column CC1 as 24' x 24' (Ag = 576 sq in) and column CC2 as 12' x 24' (Ag = 288 sq in). Both are scheduled with '#6 BARS EA CORNER' (4 bars total). The area of four...

Why it matters:

Suggested next step:

RFI draft:

Insufficient Longitudinal Reinforcement Area in Concrete Columns CC1 and CC2
Structural
Critical

Summary: ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement in nonprestressed columns to be at least 0.01Ag. The Structural Column Schedule specifies concrete column CC1 as '24' x 24' w/ #6 BARS EA CORNER' and CC2 as '12' x 24' w/ #6 BARS EA CORNER'. Providing only four #6 bars (one at each corner) yields a total steel area of...

Why it matters:

Suggested next step:

RFI draft:

Columns CC1 and CC2 have insufficient longitudinal reinforcement area
Structural
Critical

Summary: The Structural Column Schedule details concrete column CC1 as '24' x 24' w/ #6 BARS EA CORNER' (gross area Ag = 576 in²) and CC2 as '12' x 24' w/ #6 BARS EA CORNER' (gross area Ag = 288 in²). Assuming one bar per corner, this provides 4 #6 bars total per column, yielding a steel area (As) of approximately 1.76 in². ACI 318-19 Section 10.6.1.1...

Why it matters:

Suggested next step:

RFI draft:

Concrete columns CC1 and CC2 lack minimum required longitudinal reinforcement
Structural
Critical

Summary: According to ACI 318-19 Section 10.6.1.1, the area of longitudinal reinforcement for columns must be at least 0.01Ag (1% of the gross concrete area). The Structural Concrete Column Schedule specifies column CC1 as '24' x 24' w/ #6 BARS EA CORNER'. A 24' x 24' column has a gross area (Ag) of 576 sq in, requiring a minimum of 5.76 sq in of...

Why it matters:

Suggested next step:

RFI draft:

Concrete Columns CC1 and CC2 Lack Minimum Longitudinal Reinforcement
Structural
Critical

Summary: The Structural Column Schedule specifies concrete column CC1 (24' x 24') and CC2 (12' x 24') to be reinforced with '#6 BARS EA CORNER' (4 bars total). ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement to be at least 0.01Ag (1% of the gross cross-sectional area). For CC1, the minimum reinforcement is 5.76 sq in (0.01 ×...

Why it matters:

Suggested next step:

RFI draft:

Concrete Columns CC1 and CC2 violate minimum longitudinal reinforcement ratio (0.01Ag)
Structural
Critical

Summary: The Structural Column Schedule details column CC1 as 24' x 24' (Gross Area Ag = 576 sq in) and column CC2 as 12' x 24' (Gross Area Ag = 288 sq in). Both are scheduled with '#6 BARS EA CORNER', which equates to 4 total #6 bars. The area of four #6 bars is approximately 1.76 sq in. ACI 318-19 Section 10.6.1.1 requires longitudinal reinforcement...

Why it matters:

Suggested next step:

RFI draft:

Insufficient minimum longitudinal reinforcement in concrete columns CC1 and CC2
Structural
Critical

Summary: The Structural Column Schedule details concrete column CC1 as 24' x 24' (gross area Ag = 576 sq in) and CC2 as 12' x 24' (gross area Ag = 288 sq in). Both columns are scheduled with '#6 BARS EA CORNER', providing exactly 4 #6 bars (total area As = 1.76 sq in). This results in a longitudinal reinforcement ratio of approximately 0.003 for CC1 and...

Why it matters:

Suggested next step:

RFI draft:

Insufficient longitudinal reinforcement area for concrete columns CC1 and CC2
Structural
Critical

Summary: The Structural Column Schedule specifies concrete column CC1 as 24' x 24' (Ag = 576 sq in) and CC2 as 12' x 24' (Ag = 288 sq in). Both are reinforced with '#6 BARS EA CORNER', which equates to 4 #6 bars per column (totaling approximately 1.76 sq in of steel). ACI 318-19 Section 10.6.1.1 requires the area of longitudinal reinforcement to be at...

Why it matters:

Suggested next step:

RFI draft:

Missing automatic sprinkler system on level of exit discharge
General
Critical

Summary: The basement code footprint shows a seating area with an occupant load of 170. Per Section 303.1.2, since the occupant load is 50 or more, this space cannot be classified as Group B and must be classified as a Group A assembly occupancy. Under Section 903.2.1.3, an automatic sprinkler system is required throughout all stories from the Group A...

Why it matters:

Suggested next step:

RFI draft:

Elevator Opening into Stairway Enclosure or Common Shaft
Architectural
Critical

Summary: The SECOND FLOOR NOTATION PLAN shows ELEVATOR #1 and STAIR #1 directly adjacent to each other, both opening into or sharing LOBBY 201. STAIR #1 is shown with stairs leading both up and down, indicating it connects at least three stories, and it carries an 'OPEN BELOW' notation indicating it is an unenclosed floor opening at this level. Because...

Why it matters:

Suggested next step:

RFI draft:

Under-reinforced Structural Concrete Columns (CC1 & CC2)
Structural
Critical

Summary: The Structural Column Schedule specifies concrete column CC1 as '24\' x 24\' w/ #6 BARS EA CORNER' and CC2 as '12\' x 24\' w/ #6 BARS EA CORNER', which provides only 4 #6 bars per column. A #6 bar has a cross-sectional area of 0.44 sq in, yielding a total longitudinal reinforcement area of 1.76 sq in. For the 24'x24' column (gross area 576 sq...

Why it matters:

Suggested next step:

RFI draft:

Insufficient Longitudinal Reinforcement in Concrete Columns
Structural
Critical

Summary: The Structural Column Schedule specifies column CC1 as a 24' x 24' concrete column and CC2 as a 12' x 24' concrete column, both reinforced with '#6 BARS EA CORNER' (4 bars total, yielding 1.76 sq in). Under IBC Section 1901.2, structural concrete must comply with ACI 318, which mandates a minimum longitudinal reinforcement ratio of 1% of the...

Why it matters:

Suggested next step:

RFI draft:

Concrete Columns CC1 and CC2 Below Minimum Reinforcement Ratio
Structural
Critical

Summary: The Structural Column Schedule specifies concrete columns CC1 (24'x24') and CC2 (12'x24') reinforced with '#6 BARS EA CORNER' (4 bars total, providing 1.76 sq. in. of steel area). IBC Section 1901.2 requires structural concrete to be designed per ACI 318, which mandates a minimum 1% longitudinal reinforcement ratio for structural columns. The...

Why it matters:

Suggested next step:

RFI draft:

This is an anonymized example. Findings shown are excerpts for illustration. Actual project details have been modified to protect client confidentiality.

Related case studies

Similar AI plan review results by project type and discipline. Browse all case studies