Residential Renovation: 75 Issues Flagged

Check that architectural plans, sections, ventilation schedules, and wet-area details describe the same renovation scope.

Anonymized review · Published 2026-09-16

Free check on up to 10 drawing pages. Enterprise and volume pricing

Potential findings
75
Disciplines
4
Published examples
3
Critical or high examples shown
3

About this review

InspectMind ran an AI plan review on this residential set and returned 75 potential findings across Architectural, Mechanical, Electrical, Plumbing. The selected examples below show the document conflict, why it matters, and a suggested next step.

Project type
Residential
Disciplines
Architectural, Mechanical, Electrical, Plumbing
Potential findings
75
Published examples
3
Published
2026-09-16
Evidence status
Selected findings marked useful in the source review record

What this review documents

Check that architectural plans, sections, ventilation schedules, and wet-area details describe the same renovation scope.

The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.

Key findings

  1. Fireplace fuel type changes between views

    Architectural / Mechanical / Electrical / Plumbing

    High

    The floor plan specifies a gas fireplace insert while the building section at the same location specifies an electric insert.

    Next step: Confirm the appliance and coordinate gas, power, venting, and architectural details.

  2. Ridge-vent quantities do not reconcile

    Architectural

    High

    The attic schedule credits 9.13 square feet of ridge ventilation, while the two quantified roof-plan segments total 5.00 square feet.

    Next step: Reconcile the provided ventilation area with the roof layout and product rating.

  3. Shower waterproofing extent differs from specification

    Architectural / Plumbing

    High

    The specification calls for waterproofing to extend four feet beyond a curbless shower threshold. The detail appears to terminate the pan membrane at the threshold.

    Next step: Clarify the required membrane continuity and adjacent-floor waterproofing detail.

Checkers used

Issue categories

Architectural / Mechanical / Electrical / Plumbing
Architectural / Mechanical / Electrical / Plumbing findings in the selected review excerpts.
Architectural
Architectural findings in the selected review excerpts.
Architectural / Plumbing
Architectural / Plumbing findings in the selected review excerpts.

Review details and suggested questions

Fireplace fuel type changes between views

Architectural / Mechanical / Electrical / Plumbing

High

Summary: The floor plan specifies a gas fireplace insert while the building section at the same location specifies an electric insert.

Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.

Suggested next step: Confirm the appliance and coordinate gas, power, venting, and architectural details.

RFI draft: Confirm the appliance and coordinate gas, power, venting, and architectural details.

Ridge-vent quantities do not reconcile

Architectural

High

Summary: The attic schedule credits 9.13 square feet of ridge ventilation, while the two quantified roof-plan segments total 5.00 square feet.

Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.

Suggested next step: Reconcile the provided ventilation area with the roof layout and product rating.

RFI draft: Reconcile the provided ventilation area with the roof layout and product rating.

Shower waterproofing extent differs from specification

Architectural / Plumbing

High

Summary: The specification calls for waterproofing to extend four feet beyond a curbless shower threshold. The detail appears to terminate the pan membrane at the threshold.

Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.

Suggested next step: Clarify the required membrane continuity and adjacent-floor waterproofing detail.

RFI draft: Clarify the required membrane continuity and adjacent-floor waterproofing detail.

Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.