Residential Renovation: 75 Issues Flagged
Check that architectural plans, sections, ventilation schedules, and wet-area details describe the same renovation scope.
Anonymized review · Published 2026-09-16
Free check on up to 10 drawing pages. Enterprise and volume pricing
- Potential findings
- 75
- Disciplines
- 4
- Published examples
- 3
- Critical or high examples shown
- 3
About this review
InspectMind ran an AI plan review on this residential set and returned 75 potential findings across Architectural, Mechanical, Electrical, Plumbing. The selected examples below show the document conflict, why it matters, and a suggested next step.
- Project type
- Residential
- Disciplines
- Architectural, Mechanical, Electrical, Plumbing
- Potential findings
- 75
- Published examples
- 3
- Published
- 2026-09-16
- Evidence status
- Selected findings marked useful in the source review record
What this review documents
Check that architectural plans, sections, ventilation schedules, and wet-area details describe the same renovation scope.
The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.
Key findings
- High
Fireplace fuel type changes between views
Architectural / Mechanical / Electrical / Plumbing
The floor plan specifies a gas fireplace insert while the building section at the same location specifies an electric insert.
Next step: Confirm the appliance and coordinate gas, power, venting, and architectural details.
- High
Ridge-vent quantities do not reconcile
Architectural
The attic schedule credits 9.13 square feet of ridge ventilation, while the two quantified roof-plan segments total 5.00 square feet.
Next step: Reconcile the provided ventilation area with the roof layout and product rating.
- High
Shower waterproofing extent differs from specification
Architectural / Plumbing
The specification calls for waterproofing to extend four feet beyond a curbless shower threshold. The detail appears to terminate the pan membrane at the threshold.
Next step: Clarify the required membrane continuity and adjacent-floor waterproofing detail.
Checkers used
Issue categories
- Architectural / Mechanical / Electrical / Plumbing
- Architectural / Mechanical / Electrical / Plumbing findings in the selected review excerpts.
- Architectural
- Architectural findings in the selected review excerpts.
- Architectural / Plumbing
- Architectural / Plumbing findings in the selected review excerpts.
Review details and suggested questions
Fireplace fuel type changes between viewsArchitectural / Mechanical / Electrical / Plumbing
High
Architectural / Mechanical / Electrical / Plumbing
Summary: The floor plan specifies a gas fireplace insert while the building section at the same location specifies an electric insert.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Confirm the appliance and coordinate gas, power, venting, and architectural details.
RFI draft: Confirm the appliance and coordinate gas, power, venting, and architectural details.
Ridge-vent quantities do not reconcileArchitectural
High
Architectural
Summary: The attic schedule credits 9.13 square feet of ridge ventilation, while the two quantified roof-plan segments total 5.00 square feet.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Reconcile the provided ventilation area with the roof layout and product rating.
RFI draft: Reconcile the provided ventilation area with the roof layout and product rating.
Shower waterproofing extent differs from specificationArchitectural / Plumbing
High
Architectural / Plumbing
Summary: The specification calls for waterproofing to extend four feet beyond a curbless shower threshold. The detail appears to terminate the pan membrane at the threshold.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Clarify the required membrane continuity and adjacent-floor waterproofing detail.
RFI draft: Clarify the required membrane continuity and adjacent-floor waterproofing detail.
Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.
Related case studies
Similar AI plan review results by project type and discipline.
- ResidentialCalifornia Residential Renovation: 92 Issues Including Critical Structural, Code Compliance & Coordination Violations92 issues · Structural, Architectural
- ResidentialCalifornia Residential Plan Review: 87 Issues Found87 issues · Architectural, Electrical
- ResidentialResidential Horizontal Addition: 57 Issues Found57 issues · Architectural, Civil
- ResidentialLong Island Residential: 52 Issues Found52 issues · Architectural, Civil
- ResidentialADU Plan Review: 50 Issues Including Foundation Depth & Code Violations50 issues · Structural, Architectural
- ResidentialNew Orleans Residential Renovation: 44 Issues Found44 issues · Architectural, Carpentry