Extended-Stay Hotel, Ogden, UT: 472 Issues Flagged
Check snow loads, seismic systems, and veneer support on a multi-story wood-framed hotel in heavy-snow country.
Anonymized review · Published 2026-11-09
Free check on up to 10 drawing pages. Enterprise and volume pricing
- 1Critical · StructuralRoof truss snow load is below the stated design snow load
- 2High · StructuralSteel moment frame is shown without a defined seismic system
- 3High · Structural / ArchitecturalTall brick veneer has no story-by-story support
Fig. 1 · Top findings, pinned on the set
- Potential findings
- 472
- Disciplines
- 7
- Published examples
- 3
- Critical or high examples shown
- 3
Checkers used on this project
Run the same check on your set →About this review
InspectMind ran an AI plan review on this commercial set and returned 472 potential findings across Structural, Architectural, Civil, Mechanical, Plumbing, Electrical, Fire Protection. The selected examples below show the document conflict, why it matters, and a suggested next step.
- Project type
- Commercial
- Disciplines
- Structural, Architectural, Civil, Mechanical, Plumbing, Electrical, Fire Protection
- Potential findings
- 472
- Published examples
- 3
- Published
- 2026-11-09
- Evidence status
- Selected findings marked useful in the source review record
What this review documents
Check snow loads, seismic systems, and veneer support on a multi-story wood-framed hotel in heavy-snow country.
The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.
Key findings
- 1Critical
Roof truss snow load is below the stated design snow load
Structural · ASCE 7-16 Chapter 7
The design criteria give a 76 psf ground snow load and a 53 psf flat-roof snow load plus drift, but the prefabricated truss notes direct design for only 33 psf of top-chord snow load.
Next step: Revise the truss loading notes to the design snow and drift loads and check truss submittals against them.
- 2High
Steel moment frame is shown without a defined seismic system
Structural
The plans show a steel moment frame, but the design criteria list only wood shear walls as the seismic force-resisting system, and the frame column callout points to a stair detail instead of a frame detail.
Next step: Define the seismic system and coefficients for the frame and add the correct column and base details.
- 3High
Tall brick veneer has no story-by-story support
Structural / Architectural
Elevations show brick veneer running continuously to roof-bearing and parapet heights above 44 feet with no shelf angles or intermediate supports shown.
Next step: Add veneer support at floor lines with the related framing details, or document the veneer design basis.
Issue categories
- Cat. 01Structural
- Structural findings in the selected review excerpts.
- Cat. 02Structural / Architectural
- Structural / Architectural findings in the selected review excerpts.
Review details and suggested questions
01Roof truss snow load is below the stated design snow loadStructural · ASCE 7-16 Chapter 7
Critical
Structural · ASCE 7-16 Chapter 7
Summary: The design criteria give a 76 psf ground snow load and a 53 psf flat-roof snow load plus drift, but the prefabricated truss notes direct design for only 33 psf of top-chord snow load.
Why it matters: Truss suppliers design to the truss notes, so an understated snow load in a heavy-snow climate is a structural safety issue.
Suggested next step: Revise the truss loading notes to the design snow and drift loads and check truss submittals against them.
RFI draft: Revise the truss loading notes to the design snow and drift loads and check truss submittals against them.
02Steel moment frame is shown without a defined seismic systemStructural
High
Structural
Summary: The plans show a steel moment frame, but the design criteria list only wood shear walls as the seismic force-resisting system, and the frame column callout points to a stair detail instead of a frame detail.
Why it matters: A moment frame needs its own design coefficients and detailing, or a documented rule for combining systems.
Suggested next step: Define the seismic system and coefficients for the frame and add the correct column and base details.
RFI draft: Define the seismic system and coefficients for the frame and add the correct column and base details.
03Tall brick veneer has no story-by-story supportStructural / Architectural
High
Structural / Architectural
Summary: Elevations show brick veneer running continuously to roof-bearing and parapet heights above 44 feet with no shelf angles or intermediate supports shown.
Why it matters: Anchored veneer on wood-framed backing generally needs support at each story above about 30 feet, and supports are hard to add once framing is up.
Suggested next step: Add veneer support at floor lines with the related framing details, or document the veneer design basis.
RFI draft: Add veneer support at floor lines with the related framing details, or document the veneer design basis.
Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.
Related case studies
Similar AI plan review results by project type and discipline.
- CommercialMass Timber Facility, Austin, TX: 502 Issues Flagged502issues · Fire Protection, Architectural
- CommercialCommercial Mixed-Use: 316 Issues Found316issues · Architectural, Structural
- CommercialCommercial Kitchen & Multi-Discipline Plan Review: 284 Issues Found284issues · Architectural, Civil
- CommercialRetail Building, Fort Worth Metro, TX: 254 Issues Flagged254issues · Fire Protection, Architectural
- CommercialRetail Store Build-Out: 220 Issues Including Critical Egress, Fire Protection & Code Violations220issues · Fire Protection, Structural
- CommercialCommercial Cafe Renovation: 82 Issues Including Critical Fire & Electrical Violations82issues · Structural, Architectural