Extended-Stay Hotel, Ogden, UT: 472 Issues Flagged

Check snow loads, seismic systems, and veneer support on a multi-story wood-framed hotel in heavy-snow country.

Anonymized review · Published 2026-11-09

Free check on up to 10 drawing pages. Enterprise and volume pricing

472Potential findings
Flagged
  1. 1Critical · StructuralRoof truss snow load is below the stated design snow load
  2. 2High · StructuralSteel moment frame is shown without a defined seismic system
  3. 3High · Structural / ArchitecturalTall brick veneer has no story-by-story support

Fig. 1 · Top findings, pinned on the set

Potential findings
472
Disciplines
7
Published examples
3
Critical or high examples shown
3

Checkers used on this project

Run the same check on your set →
Sheet 01·Case file

About this review

InspectMind ran an AI plan review on this commercial set and returned 472 potential findings across Structural, Architectural, Civil, Mechanical, Plumbing, Electrical, Fire Protection. The selected examples below show the document conflict, why it matters, and a suggested next step.

Project type
Commercial
Disciplines
Structural, Architectural, Civil, Mechanical, Plumbing, Electrical, Fire Protection
Potential findings
472
Published examples
3
Published
2026-11-09
Evidence status
Selected findings marked useful in the source review record

What this review documents

Check snow loads, seismic systems, and veneer support on a multi-story wood-framed hotel in heavy-snow country.

The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.

Key findings

  1. 1

    Roof truss snow load is below the stated design snow load

    Structural · ASCE 7-16 Chapter 7

    Critical

    The design criteria give a 76 psf ground snow load and a 53 psf flat-roof snow load plus drift, but the prefabricated truss notes direct design for only 33 psf of top-chord snow load.

    Next step: Revise the truss loading notes to the design snow and drift loads and check truss submittals against them.

  2. 2

    Steel moment frame is shown without a defined seismic system

    Structural

    High

    The plans show a steel moment frame, but the design criteria list only wood shear walls as the seismic force-resisting system, and the frame column callout points to a stair detail instead of a frame detail.

    Next step: Define the seismic system and coefficients for the frame and add the correct column and base details.

  3. 3

    Tall brick veneer has no story-by-story support

    Structural / Architectural

    High

    Elevations show brick veneer running continuously to roof-bearing and parapet heights above 44 feet with no shelf angles or intermediate supports shown.

    Next step: Add veneer support at floor lines with the related framing details, or document the veneer design basis.

Issue categories

Cat. 01Structural
Structural findings in the selected review excerpts.
Cat. 02Structural / Architectural
Structural / Architectural findings in the selected review excerpts.

Review details and suggested questions

01
Roof truss snow load is below the stated design snow load

Structural · ASCE 7-16 Chapter 7

Critical

Summary: The design criteria give a 76 psf ground snow load and a 53 psf flat-roof snow load plus drift, but the prefabricated truss notes direct design for only 33 psf of top-chord snow load.

Why it matters: Truss suppliers design to the truss notes, so an understated snow load in a heavy-snow climate is a structural safety issue.

Suggested next step: Revise the truss loading notes to the design snow and drift loads and check truss submittals against them.

RFI draft: Revise the truss loading notes to the design snow and drift loads and check truss submittals against them.

02
Steel moment frame is shown without a defined seismic system

Structural

High

Summary: The plans show a steel moment frame, but the design criteria list only wood shear walls as the seismic force-resisting system, and the frame column callout points to a stair detail instead of a frame detail.

Why it matters: A moment frame needs its own design coefficients and detailing, or a documented rule for combining systems.

Suggested next step: Define the seismic system and coefficients for the frame and add the correct column and base details.

RFI draft: Define the seismic system and coefficients for the frame and add the correct column and base details.

03
Tall brick veneer has no story-by-story support

Structural / Architectural

High

Summary: Elevations show brick veneer running continuously to roof-bearing and parapet heights above 44 feet with no shelf angles or intermediate supports shown.

Why it matters: Anchored veneer on wood-framed backing generally needs support at each story above about 30 feet, and supports are hard to add once framing is up.

Suggested next step: Add veneer support at floor lines with the related framing details, or document the veneer design basis.

RFI draft: Add veneer support at floor lines with the related framing details, or document the veneer design basis.

Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.