Elementary School, West Virginia: 919 Issues Flagged

Check plumbing code, electrical service ratings, and storm and sanitary separation in a new school bid set.

Anonymized review · Published 2026-11-09

Free check on up to 10 drawing pages. Enterprise and volume pricing

919Potential findings
Flagged
  1. 1High · Plumbing / ArchitecturalDrinking fountains are placed inside restroom lavatory areas
  2. 2High · ElectricalMain service switchboard ratings conflict on one sheet
  3. 3High · Civil / PlumbingStorm manhole is shown at a sanitary sewer junction

Fig. 1 · Top findings, pinned on the set

Potential findings
919
Disciplines
7
Published examples
3
Critical or high examples shown
3

Checkers used on this project

Run the same check on your set →
Sheet 01·Case file

About this review

InspectMind ran an AI plan review on this education set and returned 919 potential findings across Plumbing, Electrical, Civil, Architectural, Mechanical, Structural, Fire Protection. The selected examples below show the document conflict, why it matters, and a suggested next step.

Project type
Education
Disciplines
Plumbing, Electrical, Civil, Architectural, Mechanical, Structural, Fire Protection
Potential findings
919
Published examples
3
Published
2026-11-09
Evidence status
Selected from open findings in the source review record

What this review documents

Check plumbing code, electrical service ratings, and storm and sanitary separation in a new school bid set.

The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.

Key findings

  1. 1

    Drinking fountains are placed inside restroom lavatory areas

    Plumbing / Architectural · IPC 410.5

    High

    Enlarged restroom plans show drinking fountains in the lavatory portions of two student restroom groups, while IPC 410.5 prohibits drinking fountains in public restrooms.

    Next step: Move the drinking fountains to corridor alcoves outside the restrooms and update the plumbing plans.

  2. 2

    Main service switchboard ratings conflict on one sheet

    Electrical

    High

    A tagged note calls for a 2500A switchboard rated 100 kAIC with a 2500A main breaker, while the same sheet lists a 2000A service and the one-line labels the switchboard 2000A at 65 kA.

    Next step: Confirm the service size and interrupting rating, and align the note, service data, and one-line.

  3. 3

    Storm manhole is shown at a sanitary sewer junction

    Civil / Plumbing · IPC 1101.3

    High

    The legend separates new storm and sanitary lines, but one storm manhole is drawn at a junction of storm, roof drain, and sanitary lines.

    Next step: Separate the storm and sanitary systems at this structure and revise the utility plan.

Issue categories

Cat. 01Plumbing / Architectural
Plumbing / Architectural findings in the selected review excerpts.
Cat. 02Electrical
Electrical findings in the selected review excerpts.
Cat. 03Civil / Plumbing
Civil / Plumbing findings in the selected review excerpts.

Review details and suggested questions

01
Drinking fountains are placed inside restroom lavatory areas

Plumbing / Architectural · IPC 410.5

High

Summary: Enlarged restroom plans show drinking fountains in the lavatory portions of two student restroom groups, while IPC 410.5 prohibits drinking fountains in public restrooms.

Why it matters: Relocating fountains after rough-in means new walls, piping, and alcoves.

Suggested next step: Move the drinking fountains to corridor alcoves outside the restrooms and update the plumbing plans.

RFI draft: Move the drinking fountains to corridor alcoves outside the restrooms and update the plumbing plans.

02
Main service switchboard ratings conflict on one sheet

Electrical

High

Summary: A tagged note calls for a 2500A switchboard rated 100 kAIC with a 2500A main breaker, while the same sheet lists a 2000A service and the one-line labels the switchboard 2000A at 65 kA.

Why it matters: Service gear has long lead times, and the utility application depends on the service size.

Suggested next step: Confirm the service size and interrupting rating, and align the note, service data, and one-line.

RFI draft: Confirm the service size and interrupting rating, and align the note, service data, and one-line.

03
Storm manhole is shown at a sanitary sewer junction

Civil / Plumbing · IPC 1101.3

High

Summary: The legend separates new storm and sanitary lines, but one storm manhole is drawn at a junction of storm, roof drain, and sanitary lines.

Why it matters: Storm water cannot drain into a sewer intended only for sewage.

Suggested next step: Separate the storm and sanitary systems at this structure and revise the utility plan.

RFI draft: Separate the storm and sanitary systems at this structure and revise the utility plan.

Anonymized, paraphrased excerpts from a completed project review. These three examples were selected editorially from findings the source review record kept open (not dismissed or marked wrong); that selection is not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.