Wastewater Lift Station: 372 Issues Flagged
Reconcile available fault current, equipment ratings, and motor voltages across electrical diagrams before equipment release.
Anonymized review · Published 2026-09-16
Free check on up to 10 drawing pages. Enterprise and volume pricing
- Potential findings
- 372
- Discipline
- 1
- Published examples
- 3
- Critical or high examples shown
- 3
About this review
InspectMind ran an AI plan review on this infrastructure set and returned 372 potential findings across Electrical. The selected examples below show the document conflict, why it matters, and a suggested next step.
- Project type
- Infrastructure
- Disciplines
- Electrical
- Potential findings
- 372
- Published examples
- 3
- Published
- 2026-09-16
- Evidence status
- Selected findings marked useful in the source review record
What this review documents
Reconcile available fault current, equipment ratings, and motor voltages across electrical diagrams before equipment release.
The documented result is a set of review findings. This case study does not establish that corrections were completed or that savings were realized. The examples below were marked useful in the source review record; they have been paraphrased to remove identifying details.
Key findings
- Critical
Service interrupting rating is below listed fault current
Electrical
A meter/main is labeled 10 kAIC while the listed available fault current is 22,506 amperes.
Next step: Have the electrical engineer verify the fault-current study and applicable equipment or system rating.
- Critical
Pump supply voltage changes between diagrams
Electrical
The one-line describes a 120/208-volt switchboard and 240-volt pump loads, while the drive control diagram shows a 480-volt supply from that switchboard.
Next step: Reconcile the utility supply, switchboard, drives, and motor utilization voltage.
- Critical
Main switchboard rating needs reconciliation
Electrical
A second equipment callout lists 22 kAIC against the same 22,506-ampere available fault current.
Next step: Check the complete protective arrangement and revise the rating or fault-current value as appropriate.
Checkers used
Issue categories
- Electrical
- Electrical findings in the selected review excerpts.
Review details and suggested questions
Service interrupting rating is below listed fault currentElectrical
Critical
Electrical
Summary: A meter/main is labeled 10 kAIC while the listed available fault current is 22,506 amperes.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Have the electrical engineer verify the fault-current study and applicable equipment or system rating.
RFI draft: Have the electrical engineer verify the fault-current study and applicable equipment or system rating.
Pump supply voltage changes between diagramsElectrical
Critical
Electrical
Summary: The one-line describes a 120/208-volt switchboard and 240-volt pump loads, while the drive control diagram shows a 480-volt supply from that switchboard.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Reconcile the utility supply, switchboard, drives, and motor utilization voltage.
RFI draft: Reconcile the utility supply, switchboard, drives, and motor utilization voltage.
Main switchboard rating needs reconciliationElectrical
Critical
Electrical
Summary: A second equipment callout lists 22 kAIC against the same 22,506-ampere available fault current.
Why it matters: This discrepancy leaves the design team or contractor with conflicting instructions. Resolve the governing requirement before relying on the affected documents.
Suggested next step: Check the complete protective arrangement and revise the rating or fault-current value as appropriate.
RFI draft: Check the complete protective arrangement and revise the rating or fault-current value as appropriate.
Anonymized, paraphrased excerpts from a completed project review. These three examples were marked “good catch” in the source review record; that label is feedback, not independent validation. The project total excludes duplicate-group members, dismissed findings, wrong finds, and insufficient-reference findings. Only selected excerpts are published. Customer identity, project address, source identifiers, and private drawings are omitted. Corrections, permit outcomes, and financial savings have not been independently verified. A qualified professional should assess each finding against the complete project documents.
Related case studies
Similar AI plan review results by project type and discipline.
- InfrastructureWater Treatment Plant: 562 Issues Flagged562 issues · Mechanical, Instrumentation
- MunicipalMunicipal Aquatics Center: 407 Issues Found407 issues · Architectural, Civil
- CommercialMixed-Use / Commercial: 386 Issues Found386 issues · Structural, Architectural
- Tenant ImprovementMulti-Discipline Drawing Package QA: 385 Issues Found385 issues · Architectural, Civil
- CommercialCommercial / Mixed-Use: 383 Issues Found383 issues · Civil, Structural
- CivilPlan Review: 380 Issues Found380 issues · Architectural, Civil